Option Selection; Unit Confi Guration; Valve Confi Guration - Heat Controller 7602-444 Operation Manual

Communicating service tool
Table of Contents

Advertisement

Heat Controller, Inc.
3.2

OPTION SELECTION

This option allows the confi guration of heat pump options to
be modifi ed.
Adjust the Option settings using the up/down arrow buttons.
Press the center button to select each item.
• Motorized Valve (defaults stored in control) –
valid range: Off, On
"On" delays compressor start until the valve is fully open.
Compressor ASCD (Anti-Short Cycle Delay
(default stored in control) – valid range: 5 to 8
(in 1 minute increments)
NOTE 1: The Compressor Anti-Short Cycle Delay setting
provides equipment protection by forcing the compressor to
wait a few minutes before restarting.
CAUTION!
CAUTION! This is a Commercial option only and does not
alter Residential unit operation.
3.3
UNIT CONFIGURATION
Adjust the Unit Confi guration settings including Heat
Pump Family, Heat Pump Size, Blower Type, and Loop
Confi guration using the up/down arrow buttons. Press the
center button to select each item.
Heat Pump Family (default stored in control) –
valid range: HTS, HE
Heat Pump Size (default stored in control) –
valid range: depends on Heat Pump Family setting
Blower Type (default stored in control) – valid
range: NONE, ECM
Loop Confi g (default stored in control) – valid
range: Other, MOD VALVE
3.4
VALVE CONFIGURATION
Confi gure temperature differentials at the thermostat for
Integrated Variable Speed Water Flow Control units with a
motorized modulating valve.
Adjust the Valve Confi guration settings using the up/down
arrow buttons. Press the center button to select each item.
Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
NOTE 1: Minimum and Maximum degree values are shown
only when the control is confi gured with the appropriate
values.
3.4.1
MODULATING VALVE OFF POSITION
Click Next from section 3.5 to select the off position
value for the modulating valve.
7602-444 SERVICE TOOL
MOTORIZED VALVE
COMPRESSOR ASCD
SELECT OPTION
PREVIOUS
Option Selection Menu
CURRENT CONFIG
HEAT PUMP FAMILY
HEAT PUMP SIZE
BLOWER TYPE
LOOP CONFIG
SELECT OPTION
PREVIOUS
Unit Confi guration Menu
HEATING DELTA T
COOLING DELTA T
PREVIOUS
5
OPTION SELECTION
UNIT CONFIGURATION
MODULATING VALVE
CONFIGURATION
Operating Manual
OFF
0
SELECT
SELECT
DEG
8
15
NEXT