Insufficient Airflow; Too Much Airflow - Greenheck VSU Installation, Operation And Maintenance Manual

Vsu make-up air unit with direct-fired gas heater
Table of Contents

Advertisement

Troubleshooting
Insufficient Airflow
Damper(s) not fully opened?
No
System static losses too high?
No
Blower speed too low?
No
Filters dirty or clogged
No
Leaks in ductwork
No
Belt slipping
Yes
Everything is working properly,
consult factory.
Too Much Airflow
Blower speed too high?
No
Filters not in place?
No
Insufficient external
static pressure?
No
Everything is working properly,
consult factory.
24
Model VSU Make-Up Air
Yes
Adjust damper linkage(s), or replace faulty actuator(s).
Damper actuators may take a few minutes to open.
Yes
Reduce losses by improving ductwork.
Yes
Reference: Start-Up - Blower, Air Volume Measurement and Check, pg. 14
Yes
Reference: Maintenance - Routine, Filters, pg. 31
Yes
Yes
Reference: Maintenance - Routine, V-Belt Drives, pg. 31
Yes
Reference: Start-Up - Blower, Air Volume Measurement and Check, pg. 14
Yes
Yes
Adjust drives as needed.
Clean or replace filters.
Repair leaks.
Replace or tighten belt.
Adjust drives as needed.
Install filters.
Increase external static pressure.
®