Diffuser; Remote Panel (Tscp) - Greenheck DGX Installation, Operation And Maintenance Manual

Industrial space heating
Table of Contents

Advertisement

Installation of Diffuser and Remote
Panel (TSCP)
NOTE
The location of the discharge diffuser and the TSCP
Space Heat Remote Panel are critical for optimum
performance of the Greenheat™ System.
1. Install Diffuser
Using self-tapping screws, attach diffuser to the
ductwork or unit. Be sure to maintain the recommended
floor to diffuser height. Refer to the chart for the
recommended diffuser height.
Diffuser Height (feet)
Airflow
(cfm)
Minimum
4000
15
6000
15
8000
20
10000
20
13000 -
25
20000
Thru-Wall Diffuser Height
Rooftop Diffuser Height
6
DGX Industrial Space Heating
Recommended
Maximum
20
25
20
25
20-25
30
25-30
35
30-35
40
Indoor Mounted
Unit
h
Rooftop
Unit
h
2. Install TSCP
When installing the TSCP Space Heat Remote
Panel, the location is critical to performance of the
Greenheat™ System. The TSCP should be installed five
to six feet above the floor. It is recommended that the
TSCP be installed on an outside wall, in the space, and
close to any source of infiltration such as dock doors.
DO NOT install the TSCP in the blast area of the heater
or near any other source of heat.
IMPORTANT
DO NOT install the TSCP in the blast area of the
space heater or near any other source of heat.
Recommended
TSCP Location
TSCP Location
Blast Area
®