11.5 Control Wires

The terminal layout of control wires at TB1 is shown in Table 11.10.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
The UPS, the battery cabinet, and the bypass breaker should be wired as shown in Figure
11.7.
Jumper wire if battery
OH is not applied
10
11
12
13
14
15
16
17
18
19
TB1
< UPS Cabinet >
Figure 11.7 - Connection among UPS, battery cabinet & bypass breaker
Table 11.10 External Connections
I/O
Signal Name
Output
Low Battery
Output
Backup Operation
Output
Fault
Output
Inverter Supply
Output
Warning
Input
P24
Input
Remote Run
Input
P24
Input
Remote Stop
Output
Bypass Supply
Output
Output Signal Ground
Input
P24
Input
Battery Overheat
Output
Output
52C Trip Signal
Output
Output
72B Trip Signal
Output
Output
72B Aux. Contact
.
To Bypass
Power source
for trip coil
Close at Low Battery
Close while Backup Operation
Close during Normal Operation
Close during Bypass Operation
(Ground for pin #1~5 & #10)
Shunt Trip Signal by EPO
Battery Breaker shunt trip
by EPO or Battery shutdown
Power source
TC
Input
TC
To DC
Input
< Battery Cabinet >
36
Operation
Close by Faults
Close by Warnings
Close to run UPS
Close to stop UPS
Battery's
Overheat B-contact
Bypass Breaker
Battery breaker's
Auxiliary A-contact
Bypass Breaker
Overheat
B-contact
Auxiliary A-
contact