4-2) AC OUTPUT MEASURING

TO AC RECEPTACLE
Use a circuit above for measuring AC output. A hot plate or lamp with a power factor of 1.0 may be used as a
load. Adjust the load and rpm, and check that the voltage range is as specified in the following table at the
rated amperage and rated rpm.
Model
RG2800i
RG3200i
RG4300i
RG2800iS
RG3200iS
RG4300iS

4-3) DC OUTPUT MEASURING

To DC Terminal
Measurement of DC output is executed with the switch turned ON while the current is regulated at 8.3A by
adjusting the load to the generator. If the voltage is within the range from 6V to 14V, the voltage output is
normal.
NOTE : If a battery is connected as a load to the generator, the DC output voltage will increase by
approximately 1 to 2 V.
Therefore, carefully observe the electrolyte level and do not overcharge the battery.
A
~
F
120V / 60Hz
220V / 50Hz
117-130
215-238
SWITCH
V
~
Specification
230V / 50Hz
225-248
SW
Load
– 17 –
LOAD
240V / 60Hz
235-259