Rosemount 5300 Series
Table I-1.
RB.RECOMMENDED_ACTION
I-8
Failed/Maint/Advise
Alarm Type
Active Event
None
None
Non-Volatile Writes Deferred
Advisory
Electronics Warning -
Transducer Block
PlantWeb Alerts Simulation
Probe Contamination
Configuration Error
Configuration Warning
Simulation Mode
Vapor Compensation
Maintenance
Warning
Volume/Temperature
Measurement Warning
Level / Interface
Measurement Failure
Volume / Temperature
Measurement Failure
Failed
Electronics Failure -
Transducer Block
Probe Missing
Input / Output Failure
Non-Volatile Memory Failure
Electronics Failure - Output
Board
Software Incompatible Error
Reference Manual
00809-0100-4530, Rev BA
Recommended Action
Text String
No action required
Non-volatile writes have been deferred, leave
the device powered until the advisory goes
away.
Check device installation and configuration
Use the switch on the Fieldbus electronics
board to turn simulation on or off.
Clean the probe.
Load default database to the device and
reconfigure it.
Check device configuration
Use Start / Stop Device Simulation to enable
or disable simulation.
1. Recalibrate vapor compensation.
2. Check Vapor DC configuration.
3. Check that the correct probe is attached.
1. Check volume configuration.
2. Check ambient temperature at installation
site.
3. If the surrounding temperature is OK, it
might indicate a hardware error producing
heat. Replace the transmitter head.
1. Analyze echo curve for reason and check
device configuration.
2. Check device physical installation
(for instance probe contamination).
3. Load default database to the device and
reconfigure it.
4. If error persists, it might indicate a hardware
error. Replace the transmitter head.
1. If Level Measurement Failure is active, clear
that alert first.
2. Check volume configuration.
3. Load default database to the device and
reconfigure it.
4. Check ambient temperature at installation site.
5. If error persists, it might indicate a hardware
error. Replace the transmitter head.
Replace transmitter head.
Check that the probe is properly connected.
Replace the transmitter.
1. Load default database to the device to clear
the error.
2. Download a device configuration.
3. If error persists, it may indicate a faulty
memory chip. Replace the transmitter head.
Replace the transmitter.
Replace the device.