11.3. Wiring transmission cables
Wiring method, address setting method and permissible wiring length differ according to and whether or not you are using transmission booster. Check
permissible wiring length before wiring.
A may be required depending on the number of indoor units.
Item 4 "Wiring examples" gives typical wiring examples (a-c).
a. System using remote controller (1 outdoor unit)
b. System using remote controller (system operated as a group among multiple refrigerant systems)
c. System using power supply extension unit for transmission booster (combination of systems a-b)
1 Connecting a transmission booster
A transmission booster (RP) is required when the number of connected indoor unit models in a cooling system exceeds the number of models specified
in the chart below.
* The maximum number of units that can be controlled is determined by the indoor unit model, the type of remote controller and their capabilities.
(*1)
Capability of the
connected indoor units
*1 If even one unit that is higher than 200 exists in the cooling system, the maximum capacity will be "200 or higher".
2 Name, code and possible unit connections
Name
Variable capacity unit controller
Outdoor unit
Constant capacity unit controller
Indoor unit
Indoor unit controller
Remote controller
Remote controller (*1)
Transmission booster unit
Other
*1 A transmission booster (RP) may be required depending on the number of connected indoor unit controllers.
3 Types of control cables
(1) Wiring transmission cables
•
Types of transmission cables
Shielding wire CVVS or CPEVS
•
Cable diameter
More than 1.25 mm
2
•
Maximum wiring length within 200 m
(2) Remote control cables
Kind of remote control cable
Cable diameter
Remarks
4 Wiring examples
Typical wiring examples are shown on pages 28 to 32 . (Wiring examples A ~ C)
Remote controller type
Number of connected indoor units that can be
connected without a RP.
200 or lower
200 or higher
The number of indoor units and the total number of remote controllers is displayed within the parenthesis ( ).
Code
OC
OS
IC
RC
RP
2-core cable (unshielded)
2
0.5 to 0.75 mm
When 10 m is exceeded, use cable with the same
specifications as (1) Transmission line wiring.
Prior to Ver. E
Possible unit connections
–
1 unit per 1 OC.
2 to 32 units per 1 OC (*1).
2 units maximum per group.
0 to 1 unit per 1 OC (*1).
Remote controller PAR-F 25MA
After Ver. F
16 (32)
20 (40)
16 (32)
16 (32)
27