Example Of A Design For A Fully Ducted System; Fully Ducted System - Maytag ERV-150 Installer Manual

Ventilation systems
Table of Contents

Advertisement

6.0
Installation
6.4 C
ALCULATING THE
6.4.2 Example of a design for a fully ducted system for a unit having a high
speed performance of 222 cfm
5"
5" Ø
64 cfm
5" Ø
65 cfm
6"
6" Ø
129 cfm
6" Ø
93 cfm
VI0004
6.5 I
NSTALLING THE
Never install a stale air exhaust register in a room where a combustion device is, such as a gas
furnace, a gas water heater or a fireplace.

6.5.1 Fully Ducted System

Stale air exhaust ductwork:
Install registers in areas where contaminants are produced: kitchen, bathrooms,
laundry room, etc.
Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR
install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) from the range top.
If possible, measure the velocity of the air flowing through the registers. If the velocity is high-
er than 400 ft/min. (122 m/min), then the register type is too small. Replace with a larger one.
Fresh air distribution ductwork:
Install registers in bedrooms, dining room, living room and basement.
Install registers either in the ceiling or high on the walls with air flow directed towards the
ceiling. (The cooler air will then cross the upper part of the room, and mix with room air
before descending to occupant level.)
If a register must be floor installed, direct the air flow up the wall.
(cont'd)
D
S
UCT
IZE (
CONT
(See figure 9)
4"
4" Ø
42 cfm
4"
7"
7" Ø 222 cfm
figure 9
D
R
UCTWORK AND
WARNING
!
010
(as illustrated in Section 5.1)
15
'
)
D
.
4"
4" Ø 42 cfm
4"
6" Ø 96 cfm
6" Ø 84 cfm
6"
6"
6"
7"
7" Ø 222 cfm
EGISTERS
6" Ø 138 cfm