Bryant ASPAS1BBL025 Owner's Manual page 15

25kw liquid-cooled, prepackaged standby generators
Table of Contents

Advertisement

3.1.3 15 AMP FUSE
This fuse protects the control console's DC control
circuit against electrical overload and is located inside
the control panel. If the fuse has melted open because
of an overload, engine cranking and startup cannot
occur. If the fuse needs to be replaced, use only an
identical 15-amp replacement fuse (type ATO).
3.1.4 5 AMP FUSE
This fuse protects the battery charger against electri-
cal overload and is located inside the control panel. If
the fuse needs to be replaced, use only an identical 5-
amp replacement fuse (type ATO).
This fuse will not remove the + battery input
power from the PCB when it opens. This means
the exercise timer will not be reset.
3.1.5 SET EXERCISE TIME SWITCH
This switch allows programming the generator to
start and exercise automatically. "See Weekly
Exercise Cycle."
Condition
Ready (Green)
Generator Switch is
in the OFF Mode.
System Ready for
Automatic Start
Generator Switch is
in the MANUAL Mode
Weekly Exerciser
is not set
Battery Voltage <12V
for >1 minute
Battery Voltage <6V
Unit Shutdown due
to Low Oil Pressure
Unit Shutdown due
to High Temperature
Unit Shutdown due
to Engine Overspeed
Unit Failed to Start
during it's Crank Cycle
Utility Voltage is
<45% of Nominal
Engine Speed Signal Fault
Control Board Dip Switch
is in wrong position.
NOTE:
System
Low
Bat (Red)
OFF
X
ON
X
OFF
X
X
Flashing
(-----------------------------------1 sec rate---------------------------------------)
X
ON
(Non-latching)
X
ON
OFF
X
OFF
X
OFF
X
OFF
X
Flashing
X
1 sec rate
OFF
X
OFF
X
X = indicates that the LED can be ON or OFF depending on the operating conditions.
Section 3 - Operation
Bryant Liquid-cooled 25 kW Generator
3.1.6 SYSTEM READY LED
The System Ready LED (green) has two main pro-
poses. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.
The system ready LED will be OFF when the switch
is in the manual or OFF positions.
The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.
This secondary function is only available with dip
switch two in the OFF position (ATS - automatic
transfer switch application).
Low
High
Oil (Red)
Temp (Red)
Speed (Red)
OFF
OFF
OFF
OFF
OFF
OFF
Flashing
Flashing
ON
ON
The five RED LED's will turn on one at a time
Over
Over
Crank (Red)
OFF
OFF
OFF
OFF
OFF
OFF
Flashing
Flashing
ON
ON
Flashing
Switch Position
Manual
Auto
Off
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Bryant 13