Potterton Heatmax Combi HE Range Installation & Service Instructions Manual page 30

Condensing combination boiler
Hide thumbs Also See for Heatmax Combi HE Range:
Table of Contents

Advertisement

Suggested Lifting Points
shown as shaded area
Pressure Relief Valve
30
© Baxi Heating UK Ltd 2012
Remove Sealing Caps from
under the Boiler after lifting
into position
Fig. 44
Safety Pressure
Relief
Wall Plate
10.3
1. Remove the sealing caps from the boiler connections.
NOTE: A small amount of water may drain from the
boiler once the caps are removed.
Sealing
Washers
2. Lift the boiler as indicated by the shaded areas. The boiler
should be lifted by TWO PEOPLE. Engage the slots at the
top rear of the boiler on the wall plate (Fig. 43) (see Safe
Manual Handling page 5).
3. Insert the sealing washers between the valves and pipes
on the wall plate and the boiler connections. The rubber
washers must be used on the gas connections.
4. Tighten all the connections and fit the filling loop.
Fig. 43
10.4
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the vicinity
of the boiler. Make up as much of the pipework as is
practical, including the discharge pipe supplied.
3. The pipework must be at least 15mm diameter and run
continuously downwards to a discharge point outside the
building. See section 6.7 for further details.
4. Utilising one of the sealing washers, connect the discharge
pipe to the adaptor and tighten the nut.
5. Complete the discharge pipework and route it to the
outside discharge point.
IMPORTANT: Make all soldered joints before connecting
to the pressure relief valve.
10.5
1. Connect the condensate drain to the trap outlet pipe.
Ensure the discharge of condensate complies with any
national or local regulations in force (see British Gas
"Guidance Notes for the Installation of Domestic Gas
Condensing Boilers".
2. The connection will accept 21.5mm (
pipe which should generally discharge internally into the
household drainage system. If this is not possible, discharge
into an outside drain is acceptable.
10.0 Installation
Fitting The Boiler
Fitting the Safety Pressure Relief
Discharge Pipe (Fig. 44)
Condensate Drain (see section 7.7)
/
in) plastic overflow