System Refrigerant Pressure - Bard CH3S1 Installation Instructions Manual

Chdm dehumidification module
Table of Contents

Advertisement

SYSTEM REFRIGERANT PRESSURE CHART
Return Air
Pressure
Temperature
50% RH 55% RH 60% RH 65% RH 70% RH 75% RH 80% RH
Low Side
70° DB
High Side
Low Side
75° DB
High Side
Low Side
80° DB
High Side
Low Side
85° DB
High Side
Low Side pressure: ±2°
High Side Pressure:±5°
Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V
TABLE 2
CHARGING PRESSURE LABEL
Relative Humidity %
96
97
98
248
253
258
110
112
114
270
276
282
115
119
123
297
306
315
120
127
134
342
349
356
Table is based upon rated CFM (airflow) across the Evaporator
Coil. If there is any doubt as to the correct operating charge
being in the system, the charge should be removed, system
evacuated, and recharged to serial plate instructions.
100
102
104
261
265
269
116
117
118
288
294
298
127
132
136
324
333
342
141
148
153
363
370
375
7961-679
106
273
120
303
140
351
158
380
Manual 2100-506D