  • Page 2 WARRANTY/MAINTENANCE/TROUBLE SHOOTING GUIDE WARRANTY a plastic thumb screw. 3. Remove the black flexible water tube from the nozzle at the The manufacturer guarantees the for the period of one year from top of the distribution tray (it is a push fit.), which supplies the date of purchase, the product will be free of defects in water to the distribution tray.
  • Page 3 Model 5000/6000 Flow Through Humidifiers 4. The inlet filter is located inside the black orifice fitting. Using a 6. After the test is complete firmly replace the flexible water pointy object (i.e. nail), remove the inlet. supply tube into the nozzle on the top of the distribution tray. 5.
  • Page 4 WARRANTY/MAINTENANCE/TROUBLE SHOOTING GUIDE 14. Reinstall the solenoid valve onto the humidifier side, feed the Figure 4. flexible black water supply tube back through the humidifier side, reinstall the humidifier side (if removed) onto the humidifier body and secure in place, reconnect the water supply to the solenoid valve, replace the humidifier’s front cover and secure in place, turn back on the water supply, turn back on the furnace, and turn on the humidifier...
  • Page 5 Model 5000/6000 Flow Through Humidifiers Component Parts List/ Component Warranty Recommended Item Description Humidifier Model Number Period Maintenance Duct Mount Humidity 6000 1 year Replace as required. Sensor Humidisense Electronic 5000/6000 Not Shown 1 year Replace as required. – PN 011109001 Humidifier Control Service Service Assembly –...
  • Page 6 WARRANTY/MAINTENANCE/TROUBLE SHOOTING GUIDE...
  • Page 7 Model 5000/6000 Flow Through Humidifiers...
  • Page 8: Trouble Shooting Guide

    WARRANTY/MAINTENANCE/TROUBLE SHOOTING GUIDE TROUBLE SHOOTING GUIDE water disconnect the water supply to the unit and turn the water back on. Allow the water to flow into a bucket, reconnect the water after test. MODEL 5000 AND 6000 HUMIDIFIERS • Check the amount of water being supplied to the evaporator pad.
  • Page 9 Model 5000/6000 Flow Through Humidifiers REMEDY: ducting – use hard ducting for any elbows – take the most direct route when ducting. • Adjust bypass damper to fully open position. • The bypass tube or humidifier is installed in front of air- •...
  • Page 10 WARRANTY/MAINTENANCE/TROUBLE SHOOTING GUIDE • The bypass tube or humidifier is installed in front of air- REMEDY: Wait for the furnace to be in heating mode and the green conditioning coils or is blocked in some other way – move to “humidisense”...
  • Page 11 Model 5000/6000 Flow Through Humidifiers POSSIBLE CAUSE: The humidifier is not turning off when the furnace is turning off. POSSIBLE CAUSE: Using a copper water supply tube and the water tube is touching some part of the furnace. REMEDY: See section above for solution. If the unit is running when the furnace is not in heating mode then very little water will REMEDY: If using copper water tube ensure it is not touching be evaporated and most of the water will be going down the...
  • Page 12 WARRANTY/MAINTENANCE/TROUBLE SHOOTING GUIDE MODEL 6000 HUMIDIFIERS ONLY PROBLEM: THE DIGITAL HUMIDISTAT KEEPS RESETTING TO THE DEFAULT SETTINGS. POSSIBLE CAUSE: Power source (transformer) is plugged into an outlet which is being shut off or turns off via a switch. REMEDY: Relocate the transformer to an outlet which cannot be turned off –...