Troubleshooting Ignition System - A.O. Smith VB-500, VB-750 Instruction Manual

Series 200/201 gas-fired copper boilers for hydronic heating and hot water supply
Hide thumbs Also See for VB-500, VB-750:
Table of Contents

Advertisement

FAULT DISPLAYED
"Display Fail"
Communications with UIM interrupted
Check communication cable to UIM. Try moving to other Internal Communications connector on MCB. Also check the
connectors where the cable is plugged in for best connecting wires.
"Comm. Fail Stg.*"
Communications with FCB interrupted
Same as above. Also try swapping FCB and UIM communications cables.
"Low AC Voltage"
Line voltage less than 90 vac
Check incoming power line for loss of voltage. May also be caused by a power line brown-out (momentary loss of voltage)
"Low 24VAC"
Voltage from transformer less than 18 vac
Check transformer output. Should be over 24vac. May be caused by excessive current drain or a faulty transformer
"Brown Out Reset"
Indicates a brown out reset occurred
Caused by a momentary dip in voltage on the MCB +5vdc power bus. Contact factory. (Not considered a serious problem
if it only occurs on very rare occasions.)
"Timeout Reset"
Indicates a watchdog reset occurred
Caused when the micro executes the software in an improper way. Contact factory. (Not considered a serious problem if it
only occurs on very rare occasions.)
"FCB Comm Timeout"
FCB did not receive command from MCB
Caused when communications between the MCB and the FCB are interrupted. May occur when a surge of power on a
nearby device (i.e. arc welder) creates an EMI burst. Not a serious problem if it occurs rarely.
"No Flow"
Water is not flowing
Caused by the flow switch being open when it should be closed. Check water lines, pump, flow switch contacts, wiring.
"Blower Prov Stg*
Blower pressure is too low it they should have been closed.
Check blower, switch contact, wiring, and for air leaks.
"Blocked Flue"
Flue is Blocked
Caused by the blocked flue switch contacts being open when they should have been closed. Check for flue blockage, switch
contacts, wiring.
"Blocked Inlet"
Air Inlet is blocked
Check inlet terminal, venturi screen and burner tube for debris. If inlet is clear check blocked inlet flue switch for continuity.
Inspect hose to switch to ensure it is connected and not cracked or spilt.
"High Limit"
Outlet temp. exceeded high limit setpoint
Caused when the temperature of the outlet probe exceeds the high limit setpoint. This is an internal "software" limit switch and
not an actual device. Check that the over temperature is not being caused by improper setup or operation of the boiler.
"MRHL"
Outlet temp is too high
Caused when the MRHL (a thermostat) contacts in the Outlet probe are open when they should be closed. Fault may be due
to high outlet temperature, bad switch contacts in the probe, or disconnected wiring. Note: The MRHL can be checked by
disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connector at the
end of the probe cable. The value should be approximately 0 ohms when the temperature of the probe is less than 220°F.
"Low Water"
Water level is too low
Caused by the Low Water Cut Out device not closing its feedback switch contacts when it should. Check water line, switch
contacts, wiring, LWCO.
"Low Gas"
Gas pressure is too low
Caused by the Low Gas switch being open when it should be closed. Check gas line, switch contacts, wiring.
"Powered Accessory"
Power vent not running
Caused by the Powered Vent device not closing its feedback switch contacts when it should. Could also be caused by a
problem with the relay output on the MCB. Check output to powered vent, switch contacts, wiring.
"High Gas Stg*"
Gas pressure too high
Caused by the High Gas switch being open when it should be closed. Check gas line, switch contacts, wiring.
"Inlet Probe"
Inlet probe shorted or open
Caused when the thermistor in the probe or the wiring to the probe is shorted or disconnected. Check the probe. Note: The
thermistor and wiring can be checked by disconnecting the probe from the MCB and reading the resistance across the two
active pins on the connector at the end of the probe cable. The value should be approximately 10K ohms (value will change
slightly with changes in temperature).
"Outlet Probe:"
Outlet probe shorted or open
Caused when the thermistor in the probe or the wiring is shorted or disconnected. Check the probe. Note: the thermistor and
wiring can be checked by disconnecting the probe from the MCB and reading the resistance across the two active pins on
the connector at the end of the probe cable. The value should be approximately 10K ohms (value will change slightly with
changes in temperature).
"Tank Probe"
Tank (Remote) probe shorted or open
Caused when the thermistor in the probe or the wiring is shorted or disconnected. Check the probe. Note: the thermistor and
wiring can be checked by disconnecting the probe from the MCB and reading the resistance across the two active pins on
the connector at the end of the probe cable. The value should be approximately 10K ohms| (value will change slightly with
changes in temperature).
"Igniter Stg*"
Igniter current is too low
Caused by a low current draw problem with the igniter. This may occur if the igniter is old, damaged, or disconnected and
no longer draws the proper level of current. This condition will affect the ability of the igniterto get hot enough to fire the gas
properly. Check the igniter and its associated wiring.
"Igniter Pwr Stg*"
Improper power applied to the igniter circuit
Caused by improper line power being applied to the igniter circuitry. Check line connections. Paying particular attention to
the earth ground connection. Also check that line voltage does not exceed 132 VAC RMS.
"Igniter Hdwr Stg*"
Hardware problems with igniter circuit

TROUBLESHOOTING IGNITION SYSTEM

Fault Messages and Lockout Status (* = stage number: 1, 2, 3, or 4)
DESCRIPTION
44
RED LED
LOCKOUT
Continuous
Auto Reset
Continuous
Auto Reset
Continuous
Auto Reset
Continuous
Auto Reset
- - - -
None
- - - -
None
Continuous
SOFT
Continuous
SOFT
Continuous
SOFT
Continuous
SOFT
Continuous
Auto Reset
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD
Flashing
HARD