Download Print this page

Honeywell T834L1004 - Mercury Free Cool Only Thermostat Installation Instructions

Heating and cooling thermostat

Advertisement

Quick Links

APPLICATION
The T834C Thermostat (see Fig. 1) controls 24 to 30 Vac single-stage heating-cooling systems. See Table 1 for
application information. An spdt mercury switch makes R to W on a temperature fall for heating, and R to Y on a
temperature rise for cooling.
Model No.
T834C
For use in standard heating-
cooling systems.
FAN
SWITCH
Fig. 1. T834C internal view.
® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc. •
Table 1. T834C Specifications.
Application
MOUNTING HOLE
(THERMOSTAT
TO WALL OR
OUTLET BOX)
BIMETAL ELEMENT
BEHIND SCALE
ADJUSTABLE HEAT
ANTICIPATOR
INDICATOR
SYSTEM
SWITCH
MOUNTING HOLE
TEMPERATURE
M21180
SETTING LEVER
• All Rights Reserved
T834C Heating and
Cooling Thermostat
Heat Anticipation
0.18A to 1.0A,
adjustable.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control.
INSTALLATION
When Installing This Product . . .
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
INSTALLATION INSTRUCTIONS
Switching
System
Fan
Heat-Off-
On-Auto
Cool
See Fig.
No.
2
69-1688

Advertisement

loading

Summary of Contents for Honeywell T834L1004 - Mercury Free Cool Only Thermostat

  • Page 1 3. Installer must be a trained, experienced service technician. Fig. 1. T834C internal view. 4. After installation is complete, check out the product operation as provided in these instructions. ® U.S. Registered Trademark Copyright © 2003 Honeywell International Inc. • • All Rights Reserved 69-1688...
  • Page 2 T834C HEATING AND COOLING THERMOSTAT Location To wire and mount the thermostat: 1. In replacement applications, check the existing Locate the thermostat about 5 ft (1.5m) above the floor thermostat wires for cracked or frayed insulation. on an inside wall in an area with good air circulation at Replace any wires in poor condition.
  • Page 3: Settings And Adjustments

    T834C HEATING AND COOLING THERMOSTAT SETTINGS AND ADJUSTMENTS Temperature Setting 3. Connect the ammeter between the W wire and the W terminal on the thermostat (in series with the Push the temperature setting lever to the desired control primary control). point on the temperature scale.
  • Page 4 (The mer- M2044A cury in the switch rolls to the left end of the tube.) Fig. 3. Recalibrating the thermostat. Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422...

This manual is also suitable for:

T834c