Connecting An Eva6400 Multi-Product Rack To A 0C6D Expansion Rack; Connecting An Eva8400 Multi-Product Rack To A 0C6D Expansion Rack; Connecting An Eva8400 2C18D Rack To A 0C9D Expansion Rack; Powering Up The Controllers - HP 6400/8400 Reference Manual

Enterprise virtual array expansion rack
Hide thumbs Also See for 6400/8400:
Table of Contents

Advertisement

4.
Under System Shutdown click Power Down. If you want to delay the initiation of the shutdown,
enter the number of minutes in the Shutdown delay field.
The controllers complete an orderly shutdown and then power off. The disk enclosures then power
off. Wait for the shutdown to complete.

Connecting an EVA6400 multi-product rack to a 0C6D expansion rack

Follow the procedure in
complete the expansion. You can skip the verification step

Connecting an EVA8400 multi-product rack to a 0C6D expansion rack

Follow the procedure in
complete the expansion. You can skip the verification step

Connecting an EVA8400 2C18D rack to a 0C9D expansion rack

Follow the procedure in
the expansion. You can skip the verification step

Powering up the controllers

To start a storage system, perform the following steps:
1.
Verify that each fabric Fibre Channel switch to which the HSV controllers are connected is powered
up and fully booted. The power indicator on each switch should be on.
If you must power up the SAN switches, wait for them to complete their power-on boot process
before proceeding. This may take several minutes.
NOTE:
Before applying power to the rack, ensure that the power switch on each HSV controller is
off.
2.
Power on the circuit breakers on both EVA rack PDUs. Verify that all drive enclosures are operating
properly. The status indicator and the power indicator should be on (green).
3.
Wait three minutes and then verify that all disk drives are ready. The drive ready indicator and
the drive online indicator should be on (green).
4.
Power on the upper controller (Controller A). It takes the role of master controller.
5.
Wait 10 seconds and then power on the lower controller (Controller B). It takes the role of slave
controller.
6.
Verify that the Operator Control Panel (OCP) display on each controller displays the storage
system name and the EVA WWN.
42
Connecting the main rack to the expansion rack
Connecting an EVA6400 multi-product rack to a 0C6D expansion rack
Connecting an EVA8400 multi-product rack to a 0C6D expansion rack