How to Cope with Test Run Abnormality
The phenomena from main component failure
Component
Phenomenon
Not operating
Compressor
Stop during running
High pressure error
Outdoor
at cooling
fan
Heating failure, fre-
quent defrosting
No operating sound
at applying power
Outdoor
Heating failure,
EEV
Frozen outdoor heat
exchanger part
Low pressure error
or discharge temper-
ature error
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the trou-
ble shooting guide is in the service manual
Cause
Motor insulation broken
Check resistance between terminals and
chassis
Motor insulation failure
Check resistance between terminals and
chassis
Motor failure,
Check the outdoor fan operation after being
Bad ventilation around
turned the outdoor units off for some time.
outdoor heat exchanger
Remove obstacles around the outdoor units
Bad connector contact
Check connector
Coil failure
Check resistance between terminals
EEV clogged
Service necessary
EEV clogged
Service necessary
Check method and Trouble shooting