Open/Close Suppression Toggle
If the Open/Close Suppression schedule is being used to
suppress openings, toggle this option to [Y]. If it is to sup-
press closings, toggle this option to [N].
Date Schedule
Enter the 2-digit number of the date schedule that will be
used to suppress openings or closings.
Partition Toggle
For the partitions that are to have the openings or closings
suppressed, toggle the option to [Y]
NOTE: Regardless of opening suppression, when a partition
is disarmed with alarms in memory, the opening and open-
ing after alarm reporting code will be reported, if pro-
grammed.

14.4 Arming/Disarming Schedules

Ref #: [001003]
Arming/disarming schedules are used to auto arm or auto
disarm partition(s) according to the selected date schedule.
There are 50 Arm/Disarm schedules.
The following options are programmable for each Arm/
Disarm schedule:
Date Schedule
Enter the two digit number of the Date schedule that will be
used to auto arm/disarm.
Enter Schedule [02]-[99]. Do not use schedules 00 or 01. If
these schedules are used, the arm/disarm schedule will
never activate.
Partition Toggle
Toggle the option to [Y] for the partitions that are to auto
arm or auto disarm.
Programming Date Schedule Intervals for Auto Arm/Dis-
arm:
1. Program the time to auto arm or auto disarm as the
Start time for an interval. Program the End time as one
minute after the Start time. For example, to auto arm or
auto disarm at 8 a.m., program the Start time as 0800
and the End time as 0801.
2. Select [Y] for the days of the week the partitions will
auto arm or auto disarm.
3. If the panel is not supposed to auto arm or auto disarm
on certain days, select [Y] for any Holiday Group the
schedule is to follow.
4. Finally, toggle the Auto Arm or Auto Disarm toggle
option, depending on which function the panel should
perform.
NOTE: Each interval can be used for either auto-arming or
auto-disarming, but not both.
In order for an arming/disarming schedule to function on a
partition, the following toggle options must be enabled:
• A Date schedule must be programmed with auto-arm
or auto-disarm enabled.
• Partition toggle option 'Auto-Arm /Disarm' must be
enabled.
• User function toggle option 'Auto-Arm' must be
enabled. This option has no effect on the 'Scheduled
Disarm' toggle option. To disable a scheduled disarm,
only 'Scheduled Disarm' has to be disabled.
• User function toggle option 'Scheduled Arm' or 'Sched-
uled Disarm' must be enabled.
**Not UL Listed
44
14.5 Scheduled AMS-220/220T Smoke Detector
Test
AML smoke detectors continuously monitor themselves for
low sensitivity and will report this condition as a device
trouble. In addition, this test can be conducted automati-
cally on a programmed schedule.
There are 50 smoke test schedules. Each smoke test sched-
ule is assigned a date schedule. To schedule the AML
smoke detector test, perform the following:
1. Enter reference number [001402] and press [*].
2. The keypad display will read 'Select Entry # / Enter 01-
50'. Use the arrow (< >) keys to select which Smoke Test
schedule is to be programmed and press [*}.
2. The keypad display will read 'Enter Sch.# / Enter 00-
99'. Enter the date schedule you have programmed for
the smoke test (valid entries are 02-99). The default date
schedule for each smoke test schedule is 01 (disabled).
3. The keypad display will read 'Select Toggle Partition
X'. Use the arrow (< >) keys to scroll through each parti-
tion and press the [*] key to toggle them on (Y) or off
(N). This will activate the smoke test at the pro-
grammed time for only the selected partitions. By
default, no partition is selected (N).
When programming a date schedule, program the time to
perform the AML smoke test as the Start time for an inter-
val. Program the end time as one minute after the start
time. For example, to perform a smoke test at 8 a.m., pro-
gram the Start time as 0800 and the End time as 0801.
NOTE: A different schedule must be programmed for each
partition. Each test must be programmed to occur at least
10 minutes apart.

14.6 CTT Schedule

Ref#: [001004]
CTT Schedules are to be used with the CTT duration timer
(see section 8.3). CTT schedules are used to control the time
period in which the Close Time Timer will be activated.
There are 50 CTT Schedules.
Date Schedule entry - enter the two-digit date schedule that
will correspond to the CTT time. (Section 14.1)
Partition Toggle - press the corresponding partition number
(1-8) to 'turn on' the partition that will follow the schedule.
NOTE: CTT Schedule must not be used with UL Listed Instal-
lations.

14.7 Seismic Schedule

Ref#: [001005]
Seismic schedules are used to control the time period in
which zones defined as seismic zones will be tested. There
are 50 Seismic Schedules.
Date Schedule entry - enter the two-digit date schedule that
will correspond to the time of the test.
Partition Toggle - press the corresponding partition number
(1-8) to 'turn on' the partition that will follow the schedule.