Safety Precautions - LG ARUB076BT2 Installation Manual

Multi v syncii system heat recovery outdoor unit arub series
Hide thumbs Also See for ARUB076BT2:
Table of Contents

Advertisement

Safety Precautions

Ventilate before operating air conditioner
when gas leaked out.
• It may cause explosion, fire, and burn.
If the air conditioner is installed in a small room, measures must be taken to prevent the
refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed-
ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy-
gen in the room could result.
Don't use the existing manifold gage for R22
refrigerant.
• Use the manifold gage for high pressure (R410A)
as possible as for stable refrigerant filling.
6
Outdoor Unit
Securely install the cover of control box and
the panel.
• If the cover and panel are not installed securely,
dust or water may enter the outdoor unit and fire
or electric shock may result.
Don't mix and use the R22 pipe and the
installation appliances that were used until
now
• Mixing the oil of R22 and R410A may cause
failure of the unit due to hydrolysis.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents