INSTALLATION
Continued
12
Install sediment trap in supply line as shown in
Figure 15. Locate sediment trap where it is within
reach for cleaning. Locate sediment trap where
trapped matter is not likely to freeze. A sediment
trap traps moisture and contaminants. This keeps
them from going into heater controls. If sediment
trap is not installed or is installed wrong, heater
may not run properly.
IMPORTANT: Hold the pressure regulator with
wrench when connecting it to gas piping and/or
fittings. Do not over tighten pipe connection to
regulator. The regulator body could be damaged.
Pressure
Regulator
3/8" NPT
Pipe Nipple
* A CSA design-certified equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certified equipment shutoff valve from your
dealer. See Accessories, page 26.
www.desatech.com
Tee
3"
Joint
Min
Pipe
Nipple
(4" W.C. to 10.5" W.C.
Cap
Propane/LP From External
Regulator (11" W.C. to 14"
Figure 15 - Gas Connection
Heater
Cabinet
Ground Joint
Union
Equipment
Shutoff
Valve *
Natural Gas
From Gas Meter
Pressure)
W.C. Pressure)