Combustible Materials - Desa CGCF10NR Owner's Operation And Installation Manual

Desa owner's operation and installation manual unvented (vent-free) gas compact classic hearth fireplace vmh10rnc, vmh10rpc, efs10rpa, efs10rna, cgcf10nr, c
Table of Contents

Advertisement

INSTALLATION
Continued
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabi-
net to any combustible material and wall
should follow diagram in Figure 6.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and pro-
trudes 3
1
/2" from the wall. This combustible
material must be 4" from the side of the fire-
place opening (see Figure 6).
B. Clearances from the top of the fireplace
opening to the ceiling should not be less than
36 inches.
C. For mantel clearances, see Figure 10 on
page 12.
MINIMUM CLEARANCE TO

COMBUSTIBLE MATERIALS

Top
Left and
Right Sides
36"
Example
*Minimum 16 inches from Side Wall
Figure 6 - Minimum Clearance for
Combustible to Wall
BUILT-IN FIREPLACE
INSTALLATION
Built-in installation of this fireplace involves in-
stalling fireplace into a framed-in enclosure. This
makes the front of fireplace flush with wall. An
optional trim kit accessory is available (see Ac-
cessories, page 40). Trim will extend past sides of
fireplace approximately 1/2 inch. This will cover
the rough edges of the wall opening. If installing
a built-in mantel above the fireplace, you must
follow the clearances shown in Figure 10, page
11. Follow the instructions below to install the fire-
place in this manner.
112462-01C
Bottom
and Rear
6"
0"
www.desatech.com
Height
Front Width
Depth
Bottom
1. Frame in rough opening. Use dimensions shown
in Figure 7 for the rough opening. If installing
in a corner, use dimensions shown in Figure 8
for the rough opening. The height is 26
is the same as the wall opening above.
2. If installing GA3450T blower accessory, do
so at this time. Follow instructions included
with blower accessory.
Note: If not installing blower accessory, you
may wish to run electrical wiring to your fire-
place for future blower installation (see Ac-
cessories, page 40). Use only approved three-
wire electrical wiring.
WARNING: If pre-wiring, do
not connect wiring to any elec-
trical source at this time.
Install fireplace electrical outlet
and connect wiring to outlet be-
fore connecting to electrical
source. The fireplace electrical
outlet is included with the
GA3450T blower accessory.
Only use the fireplace electrical
outlet
*
GA3450T blower accessory.
Note: A qualified installer should make all elec-
trical connections.
26
Figure 7 - Rough Opening for Installing
36
Figure 8 - Rough Opening for Installing
Actual
Framing
26"
3
26
/
"
4
1
9
/
"
2
3/4"
supplied
with
10
1
"
/
2
7
"
/
8
7
26
"
/
8
in Wall
5
"
/
8
25
26
7
"
/
8
3
51
"
/
4
in Corner
7
26
/
"
8
7
26
/
"
8
1
10
/
"
2
3/4"
7
/
" which
8
the
3/4" Off
The Floor
Minimum
7
"
/
8
11

Advertisement

Table of Contents
loading

Table of Contents