UNVENTED (VENT-FREE) LOGMATE
AIR FOR
COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside
Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see option 1, Figure 3). You can also re-
move door into adjoining room (see option
2, Figure 3). Follow the National Fuel Gas
Code NFPA 54/ANS Z223.1, Section 5.3,
Air for Combustion and Ventilation for re-
quired size of ventilation grills or ducts.
WARNING: Rework work-
sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
®
Ventilation
Grills
Into Adjoining
Room,
Remove
Option 1
Door into
Adjoining
Figure 3 - Ventilation Air from Inside Building
Outlet
Air
Inlet
Air
Figure 4 - Ventilation Air from Outdoors
Or
Room,
Option
2
Ventilated
Outlet
Attic
Air
Ventilated
Inlet Air
Crawl Space
6
®
FIREBOX
4"
To Attic
To
Crawl
Space