VENTING INSTALLATION INSTRUCTIONS
14
Installation for Vertical Termination (Cont.)
VENTING INSTALLATION
INSTRUCTIONS
Continued
Vertical Termination Configurations
Figures 21 through 24 show four different configurations for verti-
cal termination.
Venting with Two 90° Elbows
Vertical (V)
20' max.
45° Elbow
Figure 21 - Vertical Venting Configuration Using Two 90° Elbows
with Two Horizontal Runs (Vertical Round High Wind Termination
Shown)
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Horizontal (H
Horizontal (H
5' min.
2' max.
6' min.
4' max.
7' min.
6' max.
8' min.
8' max.
8' max.
Note: Install restrictor
into inner collar of
fireplace as shown.
) +
1
)
2
Figure 22 - Vertical Venting Configuration Using One 90° Elbow
(Vertical Round High Wind Termination Shown)
45° Elbow
Figure 23 - Vertical Venting Configuration Using Two 90° Elbows
(Vertical Round High Wind Termination Shown)
Venting with One 90° Elbow
Vertical (V)
5' min.
6' min.
7' min.
8' min.
20' max.
45° Elbow
Note: Install restrictor
into inner collar of
fireplace as shown.
Venting with Two 90° Elbows
Vertical (V
)
1
5' min.
6' min.
7' min.
8' min.
Note: Install restrictor
into inner collar of
fireplace as shown.
Note: Vertical (V
) + Vertical (V
1
Horizontal (H)
2' max.
4' max.
6' max.
8' max.
8' max.
Horizontal (H)
6' max.
12' max.
18' max.
20' max.
) = 40' max.
2
111250-01C