Location Of Termination Cap - Desa VT32EP Series Owner's Operation And Installation Manual

Direct-vent fireplace ng/lp “tudor” models
Table of Contents

Advertisement

LOCATION OF TERMINATION CAP

6
LOCATION OF TERMINATION CAP
D
E
V
B
L
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (305mm) minimum]
B = clearance to window or door that may be opened
[12 inches (305mm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(305mm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum]
E = clearance to unventilated soffit [12 inches (305mm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within
36 inches (914mm) horizontally from the center-line of the regulator
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
A
V
Balcony with No Side Wall
G
V
G = 12" (305mm) minimum clearance
Figure 7 - Minimum Clearances for Termination Cap
For more information, visit www.desatech.com
For more information, visit www.desatech.com
C
Fixed
Closed
Openable
F
V
B
TERMINATION CAP
V
vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow
the current National Fuel Gas Code, ANS Z223.1
Note: Local codes or regulations may require different clearances
Outside Corner
A = 6" (152mm)
Balcony with Perpendicular Side Wall
Combustible &
Noncombustible
H = 24" (610mm)
J = 20" (508mm)
B
V
V
Openable Fixed
Closed
B
J
V
X
B
A
G
AIR SUPPLY INLET
X
I = clearance to service regulator vent outlet [*72 inches (1829mm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (305mm)
minimum]
K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
minimum]
L =
clearance above paved side-walk or a paved driveway located on
public property [*84 inches (2133mm) minimum]
M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ]
N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm)
V
B = 6" (152mm)
B
H
V
J
N
H
I
G
M
V
GAS METER
RESTRICTED AREA
(TERMINATION PROHIBITED)
Recessed Location
D
C
C
E
V
C = Maximum depth of 48" (1219mm) for
recessed location
D = Minimum width for back wall of
recessed location -
Combustible - 38" (965mm)
Noncombustible - 24" (610mm)
E = Clearance from corner in
recessed location-
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)
N
G
V
G
V
X
K
A
108860

Advertisement

Table of Contents
loading

Table of Contents