VENTING INSTALLATION
INSTRUCTIONS
Continued

Horizontal termination Configurations

Figures 14 through 18 show different configurations and alterna-
tives for venting with horizontal termination. Each figure includes
a chart with critical minimum and maximum dimensions which
MUST be met. IMPORTANT: If using a venting configuration of
only horizontal venting with no vertical run, a 1/4" rise for every
12" of run toward the termination is required.
WARNING: Never run vent downward as this may
cause excessive temperatures which could cause a
fire. Operation of improperly installed and maintained
venting system could result in serious injury, property
damage or loss of life.
GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square termination (up to 12"
horizontal pipe)
• NOT FOR CORNER INSTALLATION
Adjustable
Pipe 12" Max.
Horizontal High
Wind Square
Termination
Wall Firestop
45° Elbow
Wall
Firestop
Figure 14 - Horizontal Termination Configuration for Square
and Round Terminations
10
45°
Elbow
Square Termination
Vertical (V)
Horizontal (H)
36
3
/
" min.
4
Exterior Portion of
Wall Firestop (Round
Termination Only)
Round Termination
CORNER INSTALLATION
Recommended Applications:
• Corner ground floor installation
• Ground floor installation where pipe vents horizontally through
wall (over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to
termination is possible
Wall
Firestop
Square
Termination
17" max.
Horizontal
Round
Figure 15 - Horizontal Termination Configuration for Corner
Termination
www.desatech.com
Not to Exceed
(H) Limits
45°
Elbow
Required
Vertical (V)
Vertical Pipe
*46
1
/
" min.
None
4
57
/
" min.
1 ft.
1
4
69
/
" min.
2 ft.
1
4
81
1
/
" min.
3 ft.
4
93
/
" min.
4 ft.
1
4
*
Ground Floor Corner Venting
Not to Exceed
(H) Limits
90° Elbow
Wall
Firestop
45° Elbow
Installation Using One 90° Elbow
90° Elbow
As Required for (V)
See Chart for Pipe
Section Required
Horizontal (H)
30" max.
48" max.
60" max.
84" max.
20' max.
Square
Termination
12" Minimum
111921-01E