Delta Electronics Temperature Measurement Module DVP04PT-H2 Instruction Sheet

Temperature measurement module

Advertisement

Quick Links

http://www.delta.com.tw/industrialautomation/
Temperature Measurement Module
Instruction Sheet
Warning
Please read this instruction sheet carefully before use.
Switch off the power before wiring.
DVP04PT-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or
specific tools are required to open the enclosure) in case danger and damages on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the
wiring again before switching on the power.
Do NOT touch any terminal when the power is switched on.
Make sure the ground termnial
is correctly grounded in order to prevent electromagnetic interference.
Use wires with resistance when connect the platinum resistance thermister (RTD) to PLC.
Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire to
prevent interference.
Introduction
1.1 Model Explanation & Peripherals
Thank you for choosing Delta's DVP series. DVP04PT-H2 is able to receive 4 points of platinum temperature
sensors (PT100 3-WIRE 100Ω 3850 PPM/°C (DIN 43760 JIS C1604-1989)) and convert them into 14-bit digital
signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, DVP04PT-H2 is able to read and
write the data in the module. There are 49 16-bit control registers (CR) in DVP04PT-H2.
DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
Nameplate Explanation
D e l t a P L C m o d e l n a m e
P o w e r i n p u t s p e c i f i c a t i o n
A n a l o g I / O m o d u l e s p e c i f i c a t i o n
B a r c o d e , s e r i a l N o . , V e r s i o n
VX.X X
Model/Serial No. Explanation
DVP series
H: For EH series MPU
H2: For EH2 series MPU
Points (input + output)
Model type
AD: Analog input
XA: Mixed analog I/O
DA: Analog output
HC: High-speed counter input
PT: Temperature measurement (PT-100)
PU: Single-axis position control
TC: Temperature measurement
(thermocouple)
1.2 Product Profile (Indicators, Terminal Block, I//O Terminals)
Unit: mm
1
DIN rail (35mm)
6
Terminals
2
Connection port for extension unit/module
7
Mounting hole
3
8
Model name
I/O terminals
4
POWER, ERROR, A/D indicator
9
Mounting port for extension unit/module
5
DIN rail clip
1.3 External Wiring
2007-01-10
5011651800-P2E0
power module
*1: Wiring for analog input should adopt cables of PT100 temperature sensor or double shielding cable and should be
separated from other power cables that may cause interference. Please use 3 wires for PT100.
*2: Terminal FG is the ground location for noise suppression.
*3: Please connect the
system contact or connect it to the cover of power distribution cabinet.
Note: DO NOT wire empty terminal

Specifications

2.1.
Functions
Temperature measurement
(04PT) module
Power supply voltage
Analog output channel
Applicable sensor
types
Current excitation
24Vdc 2.5W
Range of input
P T100
14 B ITS
temperature
0 4 P T - H 2 0 T 6 5 0 0 0 0 1
Range of digital
MADE I N XXXXX X
conversion
Resolution
Output impedance
Production No.
Production week
Overall accuracy
Production year (2006)
Production plant (Taoyuan)
Response time
Version No.
Isolation
Model name
Digital data format
Average function
Self-diagnosis
Protection
Communication mode
(RS-485)
When connected to
DVP-PLC MPU in
series
8
2.2.
Others
Max. rated power
consumption
Operation/storage
Vibration/shock
immunity
1mA
PT100
Shielding
cable *1
CH1
L+
L-
I-
FG
1mA
AG
PT100
Shielding
cable *1
CH4
L+
L-
I-
FG
AG
*2
Terminal of
24+
*3
System
DC/DC
AG
grounding
0V
Converter
Earth
(100
or less)
terminal on both the power module and DVP04PT-H2 to the system earth point and ground the
.
Celsius (°C)
Fahrenheit (°F)
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
4 channels/module
3-WIRE PT100Ω 3850 PPM/°C (DIN 43760 JIS C1604-1989)
1mA
-200 ~ 600
-328 ~ 1112
K-2,000 ~ K6,000
K-3,280 ~ K11,120
14 bits (0.1)
14 bits (0.18)
0.5Ω or less
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
200 ms × the number of channels
Isolation between digital area and analog area. No isolation among channels.
13 significant bits out of 16 bits are available; in 2's complement.
Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20
Upper and lower bound detection/channel
The voltage output is protected by short circuit. Please also be aware that being short
circuit for too long period of time may cause damage on internal circuit. The current
output can be open circuit.
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU.
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.
0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to
connect to MPU and will not occupy any digital I/O points.
Power Supply
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power
Environment
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity)
International standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27
(TEST Ea)
Control Registers
DVP04PT-H2
CR
RS-485
#
Parameter
Latched
Register content
address
#0
H'4064
R
Model name
#1
#2
H'4066
○ R/W CH1 average time
#3
H'4067
○ R/W CH2 average time
#4
H'4068
○ R/W CH3 average time
#5
H'4069
○ R/W CH4 average time
Average °C temp.
#6
H'406A
R
measured at CH1
5V
Average °C temp.
#7
H'406B
R
measured at CH2
AG
Average °C temp.
#8
H'406C
R
+15V
measured at CH3
Average °C temp.
-15V
#9
H'406D
R
measured at CH4
#10 ~ #11
Average °F temp.
#12
H'4070
R
measured at CH1
Average °F temp.
#13
H'4071
R
measured at CH2
Average °F temp.
#14
H'4072
R
measured at CH3
Average °F temp.
#15
H'4073
R
measured at CH4
#16 ~ #17
Present °C temp.
#18
H'4076
R
measured at CH1
Present °C temp.
#19
H'4077
R
measured at CH2
Present °C temp.
#20
H'4078
R
measured at CH3
Present °C temp.
#21
H'4079
R
measured at CH4
#22 ~ #23
Present °F temp.
#24
H'407C
R
measured at CH1
Present °F temp.
#25
H'407D
R
measured at CH2
Present °F temp.
#26
H'407E
R
measured at CH3
Present °F temp.
#27
H'407F
R
measured at CH4
#28 ~ #29
#30
H'4082
R
Error status
Communication address
#31
H'4083
○ R/W
setting
○ R/W Communication speed
#32
H'4084
(Baud Rate) setting
○ R/W Returning to default
#33
H'4085
setting
#34
H'4086
R
Firmware version
#35 ~ #48
Symbols
○: latched (when written in through RS-485 communication)
╳: non-latched
R: Able to read data by FROM instruction or RS-485 communication
W: Able to write data by TO instruction or RS-485 communication
Explanations:
1. CR#0: Model name. The user can read the model name from the program and see if the extension module
exists.
Description
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Set up by the system. DVP04PT-H2 = H'6402
Reserved
Range of settings in CH1 ~ CH4: K1 ~ K20
Default = K10
Average Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
Reserved
Average Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F
Reserved
Present Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
Reserved
Present Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F
Reserved
Register for storing all error status. See the table of error status for more
information.
For setting RS-485 communication address. Range: 01 ~ 255
Default = K1
For setting up communication speed:
4,800/9,600/19,200/38,400/57,600/115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default = H'0002
b0: 4,800 bps
b1: 9,600 bps (default)
b2: 19,200 bps b3: 38,400 bps
b4: 57,600 bps b5: 115,200 bps
b6 ~ b13: reserved
b14: High/low bit exchange of CRC checksum (only valid in RTU mode)
b15: Switch between ASCII/RTU modes; 0 = ASCII mode (default)
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
ERR LED
CH4
CH3
CH2
CH1
Take the setting of CH1 for example:
1. b0 is reserved.
2. b1 is reserved.
3. When b2 is set as 1, all the settings will return to default settings.
ERR LED definition: default of b12 ~ b15 = 1111
1. b12 corresponds to CH1. When b12 = 1 or the scale exceeds the range,
ERR LED will flash.
2. b13 corresponds to CH2. When b13 = 1 or the scale exceeds the range,
ERR LED will flash.
3. b14 corresponds to CH3. When b14 = 1 or the scale exceeds the range,
ERR LED will flash.
4. b15 corresponds to CH4. When b15 = 1 or the scale exceeds the range,
ERR LED will flash.
Displaying the current firmware version in hex; e.g. version 1.0A is indicated
as H'010A
For system use

Advertisement

loading

Summary of Contents for Delta Electronics Temperature Measurement Module DVP04PT-H2

  • Page 1: Specifications

    5011651800-P2E0 http://www.delta.com.tw/industrialautomation/ Temperature Measurement Module Instruction Sheet Warning Please read this instruction sheet carefully before use. Switch off the power before wiring. DVP04PT-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration.