Dell 3750W User Manual page 43

Online rack ups 3750w and 4200w
Hide thumbs Also See for 3750W:
Table of Contents

Advertisement

Table 6. Settings (continued)
Description
Overload Alarm Level
Power Strategy
Automatic Start Delay
Automatic on Battery Shutdown
Start on Battery
Battery Saving Mode
On Battery Notice Delay
Site Wiring Fault Alarm
Available Settings
[10%] [20%] [30%]...[100%]
If 100%, the UPS issues an Output Overload alarm
at load > 100%.
Output Overload Level 1 by default is set to
NOTE:
100% and is configurable from 10% to 100% in 10%
increments through the LCD setting menu. This
allows customers to be alerted before the UPS has
reached its rated capacity limits.
[Normal] [High Efficiency] [Converter]
See "Setting Power Strategy" on page 47.
[Off] [0s] [1s] [2s]...[32767s]
See "Configuring Load Segments" on page 49.
[Off] [0s] [1s] [2s]...[32767s]
See "Configuring Load Segments" on page 49.
[Enabled] [Disabled]
Battery start is disabled from the factory and
NOTE:
remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. After this is
set by the user, it remains set.
[Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
[0] [1s] [2s]...[99s]
The UPS issues a "UPS on battery" notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
[Enabled] [Disabled]
Default Setting
100%
High Efficiency
0s
Off
Enabled
Disabled
0s
Enabled for low
voltage models;
Disabled for all other
models
|
43
Operation