■ Specifications

Ambient operating temperature
Storage temperature
Ambient operating humidity
Storage humidity
Altitude
Operating voltage range
Rated power supply frequency
Output relays
Resistive load
Inductive load
Minimum load
Maximum contact voltage
Maximum contact current
Maximum switching capacity 1,500 VA
Mechanical life
Electrical life
Terminal screw tightening torque
Crimp terminals
Insulation resistance
Degree of protection
Case color
Case material
Weight
Mounting
Dimensions
Installation environment
Application standards
Safety standards
EMC
Cat. No. N143-E1-01
− 20 to 60°C (with no condensation or icing)
− 40 to 70°C (with no condensation or icing)
25% to 85%
25% to 85%
2,000 m max.
85% to 110% of rated operating voltage
50/60 Hz ±5 Hz (AC power supply)
6 A at 250 VAC (cos φ = 1)
6 A at 30 VDC (L/R = 0 ms)
1 A at 250 VAC (cos φ = 0.4)
1 A at 30 VDC (L/R = 7 ms)
10 mA at 5 VDC
250 VAC
6 A AC
10,000,000 operations
Make: 50,000 times, Break: 30,000 times
1.2 N·m
2
Two solid wires of 2.5 mm
, two crimp terminals of 1.5 mm
tightened together
20 M Ω (at 500 V) between charged terminals and exposed uncharged parts
20 M Ω (at 500 V) between any charged terminals (i.e., between input, output, and power
supply terminals)
Terminal section: IP20, Rear case: IP40
Munsell 5Y8/1 (ivory)
ABS resin (self-extinguishing resin) UL94-V0
200 g
Mounted to DIN Track or via M4 screws
22.5 (W) x 90 (H) x 100 (D) mm
Overvoltage Category III, Pollution Degree 2
EN60255-5/-6
EN60664-1
EMI: EN61326 Industrial applications
Electromagnetic interference wave
CISPR11 Group 1, Class A: CISPR16-1/-2
Terminal interference wave voltage
CISPR11 Group 1, Class A: CISPR16-1/-2
EMS: EN61326 Industrial applications
Electrostatic discharge EN61000-4-2: 8 kV (in air)
Radiating radio-frequency electromagnetic field EN61000-4-3:
10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz)
Burst EN61000-4-4:
Surge EN61000-4-5:
Conducted RF EN61000-4-6:
Power frequency magnetic field immunity
EN61000-4-8: 30 A/m
Voltage dip/short interruptions
EN61000-4-11: 0.5 cycle, 0.180° each, polarity 100% (rated voltage)
Single-phase Voltage Relay
2
with insulation sleeves, can be
1 kV (I/O signal line), 2 kV (power line)
1 kV with line (power line),
2 kV with ground (power line)
3 V (0.15 to 80 MHz)
K8AB-VS
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

K8ab-vsK8ab-vs1 24 vdcK8ab-vs1 24 vacK8ab-vs1 100-115 vacK8ab-vs1 200-230 vacK8ab-vs2 24 vdc ... Show all