Download Print this page

Omron CX-PROCESS Brochure page 6

Advertisement

Item
User
Online
operation
Configuration
Screen
functions
System Fixed
Screen
Batch Trend Screen
The analog signals output from each function block's tag ITEMs can be collected at fixed intervals and
stored automatically when a specified tag data condition is met. Past data can be superimposed on the chart.
Data collection
Data display
Displays the PV trend for the settings in Segment Program 2 (Block Model 157).
Segment Program
Segments can be set in table format while observing a time axis graph.
2 Screen
Data collection
Data display
Graphic Screen
This screen displays changes in the plant status using graphic elements representing plant devices pasted
to the screen from the graphic elements library. The maximum number of screens is 200.
Graphics/graphic parts: Text, straight lines, rectangles, rectangles with rounded corners, ellipses,
polygons, images
Functional Objects Provided in Library
•Fixed graphic elements provided in library: Text, instruments, thermometers, transmitters, orifices
•Variable graphic elements provided in library:
Analog display: Bar graph display, numeric indication, tanks
Analog settings: Numeric settings
Contact display: Pumps, valves, pipes
Contact operation: Switches
•Screen-displaying elements: Jump (screen jump) elements and FP switch (faceplate pop-up) elements
•Individual Graphic Screens can be imported/exported as files.
•Multiple graphic elements can be grouped and imported/exported as files.
This screen notifies the operator of alarms or errors that occur by changing the display color and emitting
Annunciator Screen
sound. A message with two lines of 16 characters each is displayed on the screen at the same time.
A total of 16 screen elements (4 columns x 4 lines) can be displayed on each screen. The maximum number
of screens is 5.
This screen displays a pre-registered message with two lines of 64 characters each
Operation Guide
together with the date of occurrence when the specified internal switch is set to ON.
Message Screen
Max. number of registerable messages: 1,000, Number of display colors: 16
Up to 1,000 messages are displayed in a single screen.
Output possible in CSV format.
A record of alarms (time of error occurrence, tag name, PV or MV current value at occurrence, alarm type,
Alarm Log Screen
etc.) that occur and that are input from the Control and Alarm blocks is saved and displayed as a list later.
Up to 1,000 alarm messages are displayed in a single screen.
Output possible in CSV format.
Operation logs of data elements and switches in Graphic Screens and a record of changes (date and time
Operation Log
of operation, tag name, original ITEM data setting, new ITEM data setting, etc.) made to ITEM data on the
Screen
Loop Control Unit/Board in the Control or Tuning Screen are saved and displayed as lists later.
Up to 1,000 operation messages are displayed in a single screen.
Output possible in CSV format.
System Monitor Screen
This screen displays the Loop Control Unit/Board system error information.
This screen displays logs of the run/stop history and a history of execution errors that occur on the Loop
System Monitor Log
Control Unit/Board together with the date and time of occurrence.
Screen
Output possible in CSV format.
Descriptions
Stores 10 days or 4 hours of data for up to 960
tags sampled at 1-minute or 1-second intervals.
Horizontal (time) axis: The time axis can be scrolled in the following time units.
1, 2, 4, 6, 8, 12, 24, 36, 48, or 72 hours
7 or 10 days
Vertical (8-point common) axis: Scale can be enlarged by a factor or 1, 2, 5 or 10.
Data is displayed from the time when the specified display start time is reached.
Display color: Red, yellow, green, blue, magenta, purple, cyan, or white
Stores 3, 30, or 180 days of data sampled at 1,
10, or 60-second intervals.
Horizontal (time) axis: The time axis can be scrolled in 2, 4, 8, 12, 24, or 72-hour time units.
Vertical axis: Scale can be enlarged by a factor or 1, 2, 5 and 10.
Data is displayed from the time when the specified display start time is reached.
Display color: Yellow, blue, green, or violet
Data can be saved manually in
CSV format by pressing a button,
or it can be saved automatically
in CSV format each time a batch is
completed. Past data is saved
automatically as binary data.
Data can be saved manually in
CSV format by pressing a button,
or it can be saved automatically
in CSV format each time a batch is
completed. Past data is saved
automatically as binary data.
7