INSTALLATION PLACES

Installation Places for Indoor unit

- There should not be any heat source or steam
near the unit.
- There should not be any obstacles to prevent the
air circulation.
- A place where air circulation in the room will be
good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into
consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the
wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
Ceiling
Ceiling Board
500 or
more
Chassis
TU/TT
TQ/TR/TP
TN/TM
* Please use an annexed sheet or the
corrugated cardboard on the bottom of
packing as installation sheet.
Annexed sheet
* When using the bottom sheet, please use it
after separating the installation sheet from
packing of the product floor by using a knife
etc as a picture below.
Ceiling Board
500 or
more
Unit : mm
Floor
H
3 300
3 600
4 200
Or
Packing corrugated
cardboard on the
bottom
INSTALLATION PLACES
Top view
Inspection hole 600 x 600
Air inlet vents
Control box
600
1 000
Air outlet vents
Side view
• Suitable dimension "H" is necessary to get a
slope to drain as shown in the figure.
* The feature can be changed according to
type of model.
[Inspection Hole Standard]
Number
Distance
of
between
Inspection
False ceiling &
hole
Actual ceiling
More than 100
1
cm
20 cm to 100
2
cm
Hole size
should be
more
Less than 20
than the
cm
size of
IDU.
11
(unit: mm)
600
Front
(unit: mm)
H=20 or more
Remarks
Sufficient space in the
ceiling for servicing.
Insufficient space.
Difficult for servicing
Minimum height for
motor replacement.