Service Diagnosis; Error Code - Haier MRV5-H Service Manual

Table of Contents

Advertisement

8. Service Diagnosis

8.1 Error Code

Failure Codes
Failure code description: (failure code of the whole system is showed as 8 bits, so 256 codes. Indoor failure code is
listed in the table and by unit number)
• Outdoor failure code exists in EEPROM, in which 5 failure codes can be kept.
• Indoor failure code exists in EEPROM, in which 5 failure codes can be kept.
• Can clear failure code by indoor or outdoor.
Failure codes are distributed as following: 0~19: indoor failure code
0~19: indoor failure code
20~99: outdoor failure code
100~109: DC motor failure code
110~125: inverter module failure code
126~127: soft auto-check failure code
Physical main unit:
Dip switch SW9, SW10, SW11 are at 0,0,0, digital tube displays failure code 20-127, it is the main failure code.
Dip switch SW9, SW10, SW11 are 1,0,0, digital tube displays failure code 20-127, it is failure code of No.1 sub unit.
Dip switch SW9, SW10, SW11 are 2,0,0, digital tube displays failure code 20-127, it is failure code of No.2 sub unit.
Physical sub unit:
Dip switch SW9, SW10, SW11 are at 0,0,0, digital tube displays failure code 20-127, it is single sub unit failure code.
Outdoor failure code display principle on wired controller:
When outdoor compressor is running, indoor wired controller will display the failure code of outdoor with higher priority.
When compressor stops, it displays all indoor failures. The indoor failures will be classified as below: sensor failure,
inverter board failure, fan motor driving board failure, any protections etc.
Digital Tube
Failure Code
Indication on
Definition
Main Unit
Defrosting temp
20-0
sensor Tdef failure
Ambient temp
21
sensor Ta failure
22-2
Ts(acc) failure
Discharging temp
23-0
sensor Td1 failure
Discharging temp
23-1
sensor Td2 failure
Modular heat
24-0
sensor Th failure
Oil temp sensor
24-1
Toil1 failure
Oil temp sensor
24-2
Toil2 failure
Inlet temp of heat
25-0
exchanger Toci1
failure
26-0
Indoor
26-1
commuication
failure
26-2
Failure Description
AD value is below 11(open circuit) or over 1012(short circuit) for 60 seconds, in
cooling mode, if the sensor is abnormal, the unit does not deal with it, besides,
in defrosting and within 3 minutes after defrosting, no alarm
AD value is below 11(open circuit) or over1012(short circuit) for 60 seconds
AD value is below 11(open circuit) or over1012(short circuit) for 60 seconds
AD value is below 11(open circuit) or over1012(short circuit) for 60 seconds
AD value is below 11(open circuit) or over1012(short circuit) for 60 seconds
AD value is below 11(open circuit) or over1012(short circuit) for 60 seconds
For continuous 200 cycles, can not find connected indoors
For continuous 270 s, the searched indoor quantity is less than the set quantity
For continuous 170 s, the searched indoor quantity is more than the set quantity
87
Remarks
Resumable