Energy Monitoring Setting; Power/Calorie; Energy Setting - LG HM121HF UB60 Owner's Manual

Air-to-water heat pump, outdoor/indoor unit
Hide thumbs Also See for HM121HF UB60:
Table of Contents

Advertisement

ENERGY MONITORING SETTING

It provides useful information on the mount of energy and power during the week/month/year.
Opening "Energy "option, these are presented on screen.

Power/Calorie

The information includes power usage / heat output produced and up to annual trend.
NOTE
• The calculated produced heat output and power are an estimation, the accuracy cannot be
guaranteed.
• The energy data should NOT be used for being invoiced or requested to government incentive
and subsidy.
• If use antifreeze agent(the antifreeze short pin(CN_ANTI_SW) must be open and switch
No.8 in Option SW 1 must be on.), then the produced heat will NOT be calculated, nor will
it be displayed on the user interface. This is because the increase of fluid viscosity makes
the accuracy of the flow measurement and thus the accuracy of heat metering unreliable.
Calibrated external meter must be used in this case.

Energy Setting

In addition, various energy settings are possible as shown below.
Current value reaches to defined target value, It alerts to you on display
ENERGY MONITORING SETTING
41