18 Installation
Recommended mounting position
1
2
1
Output terminals

Mounting plate

Non-enclosed (IP00) filters must be mounted on a grounded metal plate or cabinet
frame. Enclosed (IP22) filters can be installed to a wall without any grounded metal
plate. The structure must be of non-flammable material and strong enough to carry
the weight of the unit.

Encasing

Non-enclosed (IP00) filters must be encased or placed in a cabinet according to the
local safety requirements.

Electrical connections

Busbars are recommended for connections to the input terminals of non-enclosed
(IP00) filters.
Cables are recommended for connections to the input terminals of enclosed (IP22)
filters.
Cables must be protected for at least 105 °C (221 °F). If the filter is not installed in the
same cabinet as the drive, shielded symmetrical cable must be used between the drive
cabinet and the filter enclosure.

Free space

Free space is required around the filter for cooling as follows. The distances apply to
natural convection. With forced cooling, less free space is required.
Alternative mounting position
2
Input terminals
2
1