Daikin ARXF50A Installer's Reference Manual page 36

Table of Contents

Advertisement

6
|
Installation
Installer reference guide
36
c
a
Mounting plate (accessory)
b
Interconnection cable
c
Wire guide
2 Open the front panel, and then the service cover. Refer to
4
indoor
unit" [
 23].
3 Pass the interconnection cable from the outdoor unit through the feed-
through wall hole, through the back of the indoor unit and through the front
side.
Note: In case the interconnection cable was stripped in advance, cover the ends
with insulating tape.
4 Bend the end of the cable up.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run
parallel.
In order to avoid any electrical interference the distance between both wirings
should ALWAYS be at least 50 mm.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
a
Terminal block
b
Electrical component block
c
Cable clamp
5 Strip the wire ends approximately 15 mm.
6 Match wire colours with terminal numbers on the indoor unit terminal blocks
and firmly screw the wires to the corresponding terminals.
7 Connect the earth wire to the corresponding terminal.
8 Firmly fix the wires with the terminal screws.
9 Pull the wires to make sure that they are securely attached, then retain the
wires with the wire retainer.
10 Shape the wires so that the service cover fits securely, then close the service
cover.
a
b
FTXP50~71M2V1B + FTXF20~71A2V1B + ATXF50~71A2V1B
"6.2 Opening the
a
b
c
Daikin room air conditioner
4P513661-8H – 2019.12