Johnson Controls Z8ES Installation Manual page 29

S single-stage standard ecm residential gas furnaces
Table of Contents

Advertisement

Repeat Step 2 to Step 5 until the correct input is
achieved.
Ensure to relight any gas appliances that were
turned off at the start of this input check.
Table 9: Gas rate (cu ft/h) at full input
Time for one
Size of Test Dial
revolution
s
1 cu ft
10
360
11
327
12
300
13
277
14
257
15
240
16
225
17
212
18
200
19
189
20
180
21
171
22
164
23
157
24
150
25
144
26
138
27
133
28
129
29
124
30
120
31
116
32
113
33
109
34
106
35
103
36
100
37
97
38
95
39
92
40
90
41
88
42
86
Installation Manual: Z8ES Single-Stage Standard ECM Residential Gas Furnaces (Non-condensing Multi-position Standard
CAUTION
2 cu ft
5 cu ft
720
1800
655
1636
600
1500
555
1385
514
1286
480
1200
450
1125
424
1059
400
1000
379
947
360
900
343
857
327
818
313
783
300
750
288
720
277
692
267
667
257
643
248
621
240
600
232
581
225
563
218
545
212
529
206
514
200
500
195
486
189
474
185
462
180
450
176
439
172
429
Johnson Controls Ducted Systems
Time for one
Size of Test Dial
revolution
s
1 cu ft
50
72
51
71
52
69
53
68
54
67
55
65
56
64
57
63
58
62
59
61
60
60
62
58
64
56
66
54
68
53
70
51
72
50
74
48
76
47
78
46
80
45
82
44
84
43
86
42
88
41
90
40
92
39
94
38
96
38
98
37
100
36
102
35
104
35
2 cu ft
5 cu ft
144
360
141
355
138
346
136
340
133
333
131
327
129
321
126
316
124
310
122
305
120
300
116
290
112
281
109
273
106
265
103
257
100
250
97
243
95
237
92
231
90
225
88
220
86
214
84
209
82
205
80
200
78
196
76
192
75
188
74
184
72
180
71
178
69
173
29
and Low NOx)

Advertisement

Table of Contents
loading

Table of Contents