Fire Hazard; Burn Hazard - Carrier S4A5S Installation Instructions Manual

Horizontal air conditioner with r-410a refrigerant
Table of Contents

Advertisement

S4A5S: Installation Instructions
Operating Ambient
The minimum outdoor operating ambient in cooling mode without
accessory is 55°F (13°C).
Make Piping Connections
WARNING
!
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or
final unit disposal. Use all service ports and open all flow-control
devices, including solenoid valves.
Federal regulations require that refrigerant is not vented into the
atmosphere. Recover during system repair or final unit disposal.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
If ANY refrigerant tubing is buried, provide a 6-in (152 mm). vertical
rise at service valve. Refrigerant tubing lengths up to 36-in (914 mm).
may be buried without further special consideration. Do not bury lines
more than 36-in. (914 mm).
Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct size
and condition. Rated tubing diameters shown in
recommended up to 80 ft. (24 m). See Product Data for acceptable
alternate vapor diameters and associated capacity losses. For tubing
requirements beyond 80 ft. (24 m), substantial capacity and performance
losses can occur. Following the recommendations in the Residential
Piping and Long Line Guideline will reduce these losses. Refer to
Table 1
for field tubing diameters. Refer to
requirements.
There are no buried-line applications greater than 36-in. (914 mm)
allowed.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must
be evacuated to 500 microns to eliminate contamination and moisture in
the system.
Outdoor Unit Connected to Factory Approved Indoor
Unit
For proper unit operation, check refrigerant charge using charging
information located on control box cover and/or in the Check Charge
section of this instruction.
When outdoor unit is connect to factory-approved indoor unit, outdoor
unit contains approximate system refrigerant charge for operation with
factory approved AHRI rated indoor unit when connected by 15 ft. (4.6
m) of field-supplied or factory-accessory tubing, and factory supplied
filter drier. Check refrigerant charge for maximum efficiency.
Refrigerant Tubing Connection Outdoor
IMPORTANT: Maximum liquid-line size is 3/8-in. OD for all
residential applications including long line. Refer to Residential Piping
and Longline Guideline for further information.
IMPORTANT: Always install the factory-supplied liquid-line filter
drier. If replacing the filter drier, refer to Product Replacement Parts List.
for appropriate part number. Obtain replacement filter driers from your
distributor or branch.
Install Liquid-Line Filter Drier Indoor
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Connect vapor and liquid tubes to fittings on vapor and liquid service
valves (see
Sweat Connection
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Service valves must be wrapped in a heat-sinking material such as a wet
cloth while brazing.
Use refrigeration grade tubing. Service valves are closed from factory
and ready for brazing. Clean line set tube ends with emery cloth or steel
brush. Remove any grit or debris. Insert line set tube ends into service
valve tube stubs. Apply heat absorbing paste or heat sink product
between service valve and joint. Wrap service valves with a heat sinking
material such as a wet cloth. Braze joints using a Sil--Fos or
Phos--copper alloy. Consult local code requirements.
Refrigerant tubing and indoor coil are now ready for leak testing. This
check should include all field and factory joints.
NOTE: Some outdoor units contain a mechanical fitting at the liquid
distributor. This connection is not field serviceable and should not be
disturbed.

FIRE HAZARD

Failure to following this warning could result in personal injury, death
and/or property damage.
Table 1
are
Refrigerant and oil mixture could ignite and burn as it escapes and
contacts brazing torch. Make sure the refrigerant charge is properly
removed from both the high and low sides of the system before brazing
any component or lines.
Table 5
for accessory

BURN HAZARD

Failure to follow this caution may result in personal injury
Components will be HOT after brazing. Wear appropriate personal
protective equipment and allow to cool before handling parts and
equipment.
Table 1 – Refrigerant Connections and Recommended Liquid and
*. Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for
Notes:
1. Do not apply capillary tube to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24 and 61 m) horizontal or 35 ft. (11 m)
3. For alternate liquid line options on 18-42 size units, see Product Data or Residential
IMPORTANT: Installation of filter drier in liquid line is required.
3
Table
1.) Use refrigerant grade tubing
CAUTION
!
WARNING
!
CAUTION
!
Vapor Tube Diameters (In.)
*
LIQUID
Connection
UNIT SIZE
& Max. Tube
Diameter
18
3/8
24, 30
3/8
36, 48
3/8
60
3/8
performance data when using different size and length linesets.
vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential
Piping and Longline Guideline- Air Conditioners and Heat Pumps using Puron
refrigerant.
Piping and Application Guideline
*
RATED VAPOR
Connection
Tube
Diameter
Diameter
5/8
5/8
3/4
3/4
7/8
7/8
7/8
1-1/8

Advertisement

Table of Contents
loading

Table of Contents