Carrier 59TN6C Installation, Start-Up, Operating, Service And Maintenance Instructions page 48

Two-stage, variable-speed, multipoise 35 in. (889 mm) tall, condensing gas furnace
Table of Contents

Advertisement

59TN6C: Installation, Start-up, Operating, Service and Maintenance Instructions
1. Cut two holes, one for each pipe, of appropriate size for pipe size
being used.
2. Loosely install elbow in bracket (if used) and place assembly on
combustion-air pipe.
3. Install bracket as shown in
NOTE: For applications using vent pipe option indicated by dashed
lines in
Fig. 41
and
Fig.
42, rotate vent elbow 90_ from position.
4. Disassemble loose pipe fittings. Clean and cement using same
procedures as used for system piping. DO NOT CEMENT
POLYPROPYLENE FITTINGS.
(Direct Vent / 2-Pipe System ONLY)
When two or more furnaces are vented near each other, two vent
terminations may be installed as shown in
termination, or pair of vent terminations, must be at least 36 in. (914
mm) away from the first two terminations. It is important that vent
terminations be made as shown in
gases.
Venting System Length Calculations
The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of
elbows used in the venting system from
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer's data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one foot of
flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in
Example 1
A direct-vent 60,000 BTUH furnace installed at 2100 ft. (640M). Venting system includes FOR EACH PIPE:
70 feet (22 M) of vent pipe, 65 feet (20 M) of combustion air inlet pipe, (3) 90º long-radius elbows, (2) 45º long-radius elbows, and a factory accessory
concentric vent kit.
Can this application use 2" (50 mm ND) PVC/ABS DWV vent piping?
Measure the required linear length of air inlet and vent
pipe; insert the longest of the two here
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the vent or
inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the vent or
inlet pipe)
Add equiv length of factory concentric vent term
Add correction for flexible vent pipe, if any
Total Equivalent Vent Length (TEVL)
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig. 41
and
Fig.
50.
Fig.
41, but next vent
Fig. 41
to avoid recirculation of vent
Table
15.
3
2
Inducer Outlet Restrictor
To improve efficiency and operation of 40K, 60K or 100K BTUH input
models on very short vent systems, an inducer outlet restrictor is
required to be installed on the outlet of the inducer assembly. The outlet
restrictor is shown in the footnote of
Vent Length. The outlet restrictor for 40K models is shipped in the loose
parts bag. See
Table 14
100K inducer outlet restrictors.
To determine if the outlet restrictor is required, see
Failure to use an outlet restrictor on the 40K model when required may
result in flame disturbance or flame sense lockout.
To install the outlet restrictor:
1. Remove the vent elbow from the inducer outlet.
2. Align the lock tabs on the outlet restrictor with the slots on inside
outlet of the inducer assembly.
3. Snap the outlet restrictor in place.
4. Re-install the vent elbow.
5. Torque vent elbow clamp 15-lb-in.
Table
14.
70 ft.
(22 M)
3 ft.
9 ft.
x
=
(0.9 M)
(2.7 M)
1.5 ft.
3 ft.
x
=
(0.5 M)
(0.9 M)
0 ft.
0 ft.
82 ft.
(25 M)
95 ft.
(29 M)
YES
48
Table 14
-Maximum Equivalent
for usage, part numbers and sourcing of 60K and
Table
Use length of the longer of the vent
or air inlet piping system
From
Table 15
From
Table 15
From
Table 15
From Vent Manufacturer's
instructions; zero for PVC/ABS DWV
Add all of the above lines
For 2" pipe from
Table 14
Therefore, 2" pipe MAY be used