Emergency stop, stop category 0 (option
+Q951) for ACS880 multidrives
User's manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS880

  • Page 1 — OPTIONS FOR ABB DRIVES Emergency stop, stop category 0 (option +Q951) for ACS880 multidrives User's manual...
  • Page 3 Emergency stop, stop category 0 (option +Q951) for ACS880 multidrives User's manual Table of contents 1. Safety instructions 4. Electrical installation 6. Start-up and acceptance test © 2019 ABB Oy. All Rights Reserved. 3AUA0000119885 Rev F EFFECTIVE: 2019-06-28...
  • Page 5: Table Of Contents

    Hardware settings ................4 Electrical installation Contents of this chapter ................Wiring ....................Customer-installed main breaker in liquid-cooled ACS880 multidrives ....5 Use of the safety function Contents of this chapter ................Activating the safety function ..............Resetting the safety function ..............
  • Page 6 6 Table of contents Reporting problems and failures related to safety functions ........ 8 Maintenance Contents of this chapter ................Safety circuit maintenance ..............Proof test interval ................. Competence ..................Residual risk ..................Intentional misuse ................Decommissioning ................. 9 Technical data Contents of this chapter ................
  • Page 7: Safety Instructions

    Safety instructions 7 Safety instructions Contents of this chapter This chapter contains the safety instructions which you must obey when you install, operate and do maintenance on the safety functions of a drive. Use of warnings and notes Warnings tell you about conditions which can cause injury or death, or damage to the equipment.
  • Page 8: Electrical Safety Precautions

    8 Safety instructions Only a qualified electrician who has appropriate knowledge on functional, machine, and process safety is allowed to install, start up and maintain the safety circuit. All user-made changes are on the user's responsibility. WARNING! Always test the operation of the safety circuit according to its acceptance test procedure at the start-up and after any changes to the safety circuit.
  • Page 9: Introduction To The Manual

    Exclusion of liability ABB is not responsible for the implementation, verification and validation of the overall safety system. It is the responsibility of the system integrator (or other party) who is responsible for the overall system and system safety.
  • Page 10: Quick Reference Guide For Taking A Safety Function Into Use

    Related manuals Manual Code Drive hardware Mechanical installation instructions for ACS880 multidrive cabinets 3AUA0000101764 Electrical planning instructions for ACS880 multidrive cabinets and modules 3AUA0000102324 Supply units ACS880-207 IGBT supply units hardware manual 3AUA0000130644 ACS880-307 (+A003) diode supply units hardware manual...
  • Page 11: Terms And Abbreviations

    You can find manuals and other product documents in PDF format on the Internet. See Document Library. For manuals not available in the Document library, contact your local ABB representative. For additional ABB safety information and solutions visit http://www.abb.com/safety. Terms and abbreviations Term Description Cat.
  • Page 13: Option Description

    Option description 13 Option description Contents of this chapter This chapter describes the +Q951 emergency stop option and its settings. Overview Option +Q951 corresponds to an uncontrolled stop in accordance with stop category 0 (EN/IEC 60204-1). After the emergency stop command has been given, the drive trips the main contactor/breaker which cuts off the input power of the drive.
  • Page 14 14 Option description -F61 -F61 -T61 -T61 -T61 -A41 -A41 DI4 (E-stop ) DI4 (E-stop ) -K65 -S62 -S62 -T11.x -T11.x XSTO XSTO -K64 -K64 -K64 -X51 B -X51 B -X52 B -X52 B XSTO XSTO .OUT .OUT SGND SGND SGND SGND SGND...
  • Page 15: Fault Reaction Function

    Note: Resetting the safety function is not possible, if the reset circuit in the emergency stop safety relay is open. Parameter settings Note: ACS880 primary control program controls the inverter unit by default. There are dedicated control units for the supply and inverter units. The inverter unit parameter settings in ACS880 primary control program: •...
  • Page 16: Hardware Settings

    16 Option description • parameter 31.22 STO indication run/stop is set to value Warning/Warning (recommended). The supply unit parameter settings in the ACS880 supply control programs: • parameter 121.04 Emergency stop mode is set to value Stop and warning •...
  • Page 17: Electrical Installation

    Electrical installation 17 Electrical installation Contents of this chapter This chapter describes the wiring of the safety option done at the factory and contains guidelines for making user connections (if any). Wiring If option +G331 has been selected, one emergency stop button and one reset button are installed on the cabinet door and wired to the drive at the factory.
  • Page 18: Customer-Installed Main Breaker In Liquid-Cooled Acs880 Multidrives

    ■ Customer-installed main breaker in liquid-cooled ACS880 multidrives Liquid-cooled ACS880 multidrives can be delivered without a factory-installed main breaker. In these cases, customer must install and connect the main breaker to the safety circuit as described in the circuit diagrams.
  • Page 19: Use Of The Safety Function

    Use of the safety function 19 Use of the safety function Contents of this chapter This chapter describes the use of the safety function with factory default settings. Activating the safety function 1. Push the emergency stop button [S61]. The emergency stop is activated and the button locks in the “ON”...
  • Page 21: Start-Up And Acceptance Test

    Start-up and acceptance test 21 Start-up and acceptance test Contents of this chapter This chapter describes the start-up, acceptance test procedure, and validation of the safety function. Validation of the safety functions You must do an acceptance test (validation) to validate the correct operation of safety functions.
  • Page 22: Acceptance Test Reports

    Check the parameters that are relevant to the safety function. If necessary, set the parameters as defined in section Parameter settings. Note: ACS880 primary control program controls the inverter unit by default. There are dedicated control units for the supply and inverter units.
  • Page 23 Start-up and acceptance test 23 Action We recommend that you monitor these signals with the Drive composer PC tool: • 01.01 Motor speed used (rpm) • 01.02 Motor speed estimated (rpm) • 01.07 Motor current (A) • 01.10 Motor torque (%) •...
  • Page 25: Fault Tracing

    If the emergency stop safety relay cannot be reset, check the reset circuit connections. For more fault tracing possibilities, see the hardware and firmware manuals of the drive. Reporting problems and failures related to safety functions Contact ABB.
  • Page 27: Maintenance

    If you change any wiring or component after the start-up or restore parameters to their factory default values: • Use only ABB-approved spare parts. • Register the change to the change log for the safety circuit. •...
  • Page 28: Competence

    28 Maintenance (high or low demand as defined in IEC 61508, EN/IEC 62061 and EN ISO 13849-1). Regardless of the mode of operation, it is a good practice to check the operation of the safety function at least once a year by doing the start-up and acceptance test of the safety function.
  • Page 29: Technical Data

    A. ■ Safety block diagrams Each multidrives delivery is unique. If included in the customer order, ABB defines the safety block diagram for the safety function and delivers the diagram separately to the customer. ■ Relevant failure modes Relevant failure modes are: •...
  • Page 30: Fault Exclusions

    30 Technical data • internal failures of safety relays and the emergency stop button. These failures are included in the PFH value of the function. ■ Fault exclusions Fault exclusions (not considered in the calculations): • any short and open circuits in the cables of the safety circuit •...
  • Page 31: Compliance With The European Machinery Directive

    Technical data 31 Standard Name 2006/42/EC European Machinery Directive Other Machine-specific C-type standards Compliance with the European Machinery Directive The drive is an electronic product which is covered by the European Low Voltage Directive. However, the drive internal safety function of this manual is in the scope of the Machinery Directive as a safety component.
  • Page 33: Further Information

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 34 3AUA0000119885F © 2019 ABB Oy. All Rights Reserved. Specifications subject to change without notice.