Mitsubishi Electric Mr. SLIM Mr. SLIM S KA Series Installation Manual page 15

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
6. Electrical work
If the indoor and outdoor units have separate power supplies, refer to the table
at the below. If the optional wiring replacement kit is used, change the indoor unit
electrical box wiring referring to the figure in the right and the DIP switch settings of
the outdoor unit control board.
Indoor power supply terminal kit (option)
Indoor unit electrical box connector
connection change
Label affixed near each wiring diagram for
the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main power switch (Breaker)
Indoor unit power supply & earth
Indoor unit earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Wired remote controller (option) Indoor unit
Indoor unit L-N
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Wired remote controller (option) Indoor unit
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 120 m
For PUHZ-RP/PUZ-ZM100/125/140 YHA application, use shield wires. The shield part must be grounded with the indoor unit OR the outdoor unit, NOT with both.
*3. Max. 500 m
(When using 2 remote controllers, the maximum wiring length for the remote controller cables is 200 m. If 2 remote controllers are connected, set one to "Main" and the other to "Sub". For setting
procedures, refer to "Initial settings" in the installation manual for the remote controller.)
*4. The figures are NOT always against the ground.
*5. It depends on the outdoor unit.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245
IEC 57)
3. Install an earth longer than other cables.
4. Wiring for remote controller cable shall be apart (50 mm or more) from power source wiring so that it is not influenced by electric noise from power
source wiring.
Warning:
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.
Indoor unit specifications
Required
Required
Required
ON
3
OFF
1
2
(SW8)
PKA-M·KA(L) Series
~/N (single), 50/60 Hz, 230 V
*1
*2
*3
2 × Min. 0.3 (Non-polar)
*4
*4
*4 *5
24V DC/28V DC
*4
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)
L
N
BLACK
CN01
Indoor unit
S1
control board
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
16 A
3 × Min. 1.5
1 × Min. 1.5
2 × Min. 0.3
230V AC
12V DC
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
Connectors
L
N
BLACK
CN01
Indoor unit
S1
control board
S2
S3
Separate indoor unit/outdoor unit power
supplies
13
en

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr. slim mr. slim s kal series

Table of Contents