Performance Curves - Mitsubishi Electric MXZ-2F33VF4-E1 Service Manual

Table of Contents

Advertisement

9

PERFORMANCE CURVES

MXZ-2F33VF
MXZ-2F42VF
MXZ-2F33VF2
MXZ-2F42VF2
MXZ-2F33VF3
MXZ-2F42VF3
MXZ-2F33VF4
MXZ-2F42VF4
MXZ-3F54VF
MXZ-3F68VF
MXZ-3F54VF2
MXZ-3F68VF2
MXZ-3F54VF3
MXZ-3F68VF3
MXZ-3F54VF4
MXZ-3F68VF4
MXZ-4F83VF
MXZ-5F102VF
MXZ-4F83VF2
MXZ-5F102VF2
MXZ-2F53VFHZ MXZ-4F83VFHZ
MXZ-2F53VFHZ2 MXZ-4F83VFHZ2
The standard specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed, the following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 - 264 V 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature:
(2) Indoor outlet air wet-bulb temperature:
(3) Outdoor intake air dry-bulb temperature:
(4) Total input:
(5) Indoor intake air dry-bulb temperature:
(6) Outdoor intake air wet-bulb temperature:
(7) Total input:
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at
service.
How to measure the indoor air wet and dry bulb temperature difference
1.
Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2.
Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3.
Check that the air filter is cleaned.
4.
Open windows and doors of room.
5.
Press the emergency operation switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6.
When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7.
10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
Wet and dry bulb
thermometers
FRONT VIEW
OBH790L
MXZ-2F53VF
MXZ-2F53VFH
MXZ-2F53VF2
MXZ-2F53VFH2
MXZ-2F53VF3
MXZ-2F53VFH3
MXZ-2F53VF4
MXZ-2F53VFH4
MXZ-4F72VF
MXZ-4F72VF2
MXZ-4F80VF2
MXZ-4F72VF3
MXZ-4F80VF3
MXZ-4F72VF4
MXZ-4F80VF4
MXZ-6F120VF2
MXZ-6F122VF
°CWB
}
°CWB
Cooling
°CDB
W
}
°CDB
°CWB
Heating
W
122
OUTDOOR UNIT
Wet and dry bulb
thermometers
BACK VIEW