CHARGING WITH GAUGES
CAUTION
!
Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.
All units include a cooling charging chart for cooling. The heating
charging charts in Table 3 through Table 10 in this document use the
chart corresponding to the installed indoor coil. It can also be obtained
at
www.upgnet.com
under the Service Application Data section.
CAUTION
!
Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.
TABLE 3: YHE18 Heat Charging Charts
YHE/TH4/RHP14L18
Ambient Temperature (°F)
CFM
Indoor Temperature (°F)
450
Liquid Pressure (PSIG)
600
Liquid Pressure (PSIG)
750
Liquid Pressure (PSIG)
-
Suction Pressure (PSIG)
YHE/TH4/RHP14L18
Ambient Temperature (°F)
CFM
Indoor Temperature (°F)
450
Liquid Pressure (PSIG)
600
Liquid Pressure (PSIG)
750
Liquid Pressure (PSIG)
-
Suction Pressure (PSIG)
TABLE 4: YHE24 Heat Charging Charts
YHE/TH4/RHP14L24
Ambient Temperature (°F)
CFM
Indoor Temperature (°F)
600
Liquid Pressure (PSIG)
800
Liquid Pressure (PSIG)
1000
Liquid Pressure (PSIG)
-
Suction Pressure (PSIG)
YHE/TH4/RHP14L24
Ambient Temperature (°F)
CFM
Indoor Temperature (°F)
600
Liquid Pressure (PSIG)
800
Liquid Pressure (PSIG)
1000
Liquid Pressure (PSIG)
-
Suction Pressure (PSIG)
8
CF/CM/CU18, AP18B, AE18B, AVC18B, RFCX18B(P,E)
60
47
60
70
80
60
70
80
381 427 472 351 394 436
345 389 434 319 355 404
309 352 395 286 329 372
136
111
CF/CM/CU24, AP24B, AE24B, AVC24B, RFCX24BE
60
47
60
70
80
60
70
80
387 434 480 357 400 444
351 396 441 324 361 411
315 358 402 291 335 378
145
119
CF/CM/CU24, AP24B, AE24B, AVC24B, RFCX24B(P,E)
60
47
60
70
80
60
70
80
399 449 498 368 418 467
359 407 454 335 366 431
319 365 410 301 348 394
136
109
CF/CM/CU30, AP30, AE30, AVC30, RFCX30B(P,E)
60
47
60
70
80
60
70
80
378 425 472 349 396 443
340 385 430 318 347 409
302 346 389 285 329 374
136
111
Before using gauges, confirm that your gauges are accurate by
comparing the gauges against a calibrated pressure gauge that
has been calibrated against a national standard. If a calibrated
pressure gauge is not available, place a R-410A virgin refrigerant
container in a conditioned space long enough to come to tempera-
ture equilibrium with the surroundings. Then measure the tem-
perature of the air and the pressure of the refrigerant and compare
it to the following table:
:
TABLE 2: R-410A Saturation Properties
Temp
Pressure
(°F)
(Psig)
40
119
45
130
50
143
55
156
60
170
65
185
70
201
Before measuring the pressures, use the method above to check the air
flow and then consult the table and match the liquid pressure to that air
flow.
Reference the heat charging charts in Table 3 through Table 10
40
30
60
70
80
60
70
336
384
432
318 363 409 274 324
308
354
400
294 338 382 263 308
281
325
369
270 313 356 251 292
97
80
40
30
60
70
80
60
70
342
390
439
323 370 416 278 330
314
360
407
299 344 389 267 313
286
330
375
275 318 362 256 297
104
85
40
30
60
70
80
60
70
353
401
449
332 380 427 298 344
322
358
415
306 352 397 280 323
292
337
382
280 324 367 262 302
96
80
40
30
60
70
80
60
70
335
380
426
315 360 405 283 326
305
339
393
290 333 376 265 306
277
320
362
265 307 348 248 286
97
80
Temp
Pressure
Temp
(°F)
(Psig)
(°F)
75
218
110
80
236
115
85
255
120
90
274
125
95
295
130
100
317
105
341
17
80
60
70
80
60
375
276
354
259
333
243
59
17
80
60
70
80
60
381
280
360
264
339
247
63
17
80
60
70
80
60
389
286
365
269
342
253
60
17
80
60
70
80
60
369
271
346
255
324
240
59
Johnson Controls Ducted Systems
Pressure
(Psig)
365
391
418
447
477
.
10
70
80
318
361
300
342
283
322
52
10
70
80
324
367
306
347
288
328
55
10
70
80
331
375
312
354
293
333
52
10
70
80
313
356
295
336
278
316
52