Page 1
SERVICE MANUAL Model AS25XCHHRA-NR AS35XCHHRA-NR QUIET MODE I FEEL HEALTH AIRFLOW HEALTH SLEEP TURBO SELF EXTRA CLEAN ECOSENSOR FUNCTION LOCK LIGHT RESET WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public.
Introduction 1 Introduction 1.1 Model name explanation series Apply toT1; 220~240V50HZ/1ph DC inverter Indoor units Version number 40X Platform Platform of indoor units: X (X platform) Nominal cooling capacity (9000TU/h) Type of indoor unit: S (wall-mounted) Indoor unit series Apply toT1; 220~240V50HZ/1ph DC inverter Indoor units Version number...
Wi-Fi Control Download the Haier hOn App to an Apple or Android smart device, and link the equipment to the smart device for system control from whenever and wherever you want.
Specifications TECHNICAL SPECIFICATIONS-PARTS 20/25 cooling cooling heating heating Type Cross flow fan Motor output Air flow rate(high) m³/h Speed(Hi/Mid/Lo) 1200/1000/800 1100/950/800 Type ML fin- 5HI-HX tube Heat exchanger Segment *stage*fitch 3*20*1.4 Air direction control Right,Left,Horizontal,Downward Removable/Washable/Mildew Proof Air filter Microcomputer Control Temperature control Note: the data are based on the conditions shown in the table below Conversation formulae...
OFF ON 3 ON ON OFF OFF B 4 ON OFF ON OFF 2 N_RC RC 35 33 DISPLAY SERIES 387/989 325/498 UNIT MOUDLE PCB MOUDLE DISPLAY MOUDLE 0011800989 ON OFF AS25XCHHRA-NR 0011801123E(23) AS35XCHHRA-NR 0011800989 ON OFF 0011801123E(26) Domestic air conditioner...
Page 15
Functions and Control 7.Funcitions and Control 7.1 Main functions and control specification 7.1.1 Automatic operation When the running mode is turned to automation after starting the system, the system will first determine the running mode according to the current room temperature and then will run according to the determined mode.
Functions and Control Control feature: send the dehumidifying signal to the outdoor system. When Tr>Ts+2℃, the compressor will be turned on, the indoor fan will operate at the set speed. When Tr is between the Ts and Ts+2℃, the outdoor system will operate at the high dehumidifying frequency for 10 minutes and then at the low dehumidifying mode for six minutes.
Page 17
Functions and Control 7.1.4 Heating operation mode. * temperature control range: 16---30℃ * temperature difference: ±1℃ * control feature: the temperature compensation is automatically added and the system will send the heating signals to the outdoor system. If Tr+0.5℃≤Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode. If Tr>Ts+1.5℃, the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
Page 18
Functions and Control Send strength operation signal to the outdoor system. The mode change finishes the strength operation. Entering ‘mute’, you can have normal operation or signal control such as timing to finish the strength operation. When the system is at the automatic option with the strength/ mute function, if the system enters the cooling mode, the cooling strength/ mute function will be offered;...
Page 19
Functions and Control operations, the set temperature will be raised for 1 centigrade and the system will keep this status for 3 hours and then close down. 2.3 During the dormant time, except the change of the system mode or a new press on the dormant setting keys, the timing of the 8 hours dormancy will take the first timing as the start time, any presses on other keys will not affect the original timing.
Page 20
Functions and Control 7.1.12 High load protection control The outdoor system will be stopped if the coil temperature is above 63℃ for 2 minutes. The indoor fan will be controlled by the thermostat. The outdoor system can be restarted when the coil temperature is below 45℃...
Page 21
Functions and Control 7.1.16 Single indoor system operation * Enter condition: First, set the high speed airflow and 30 centigrade set temperature, then press the dormant keys for 6 times within 7 seconds, the system will feedback with 6 rings. * After the system enters the separate indoor system operation mode, the indoor system will operate according to the set mode and neglect the communication signals of the outdoor system.
Page 22
Functions and Control 7.2 Value of thermistor Room sensor and Pipe Sensor R25℃=10KΩ B25℃/50℃=3700K Temp.((℃)) Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance(℃) 165.2170 147.9497 132.3678 -1.94 1.75 155.5754 139.5600 125.0806 -1.93 1.74 146.5609 131.7022 118.2434 -1.91 1.73 138.1285 124.3392 111.8256 -1.89 1.71 130.2371 117.4366 105.7989 -1.87...
Service Diagnosis 10 Service Diagnosis 10.1 Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1.When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.When a signal transmission error occurs between the indoor and outdoor units.In either case, conduct the diagnostic procedure described in the following pages.
Page 29
Service Diagnosis Error Codes and Description indoor display 10.4 Split board: LED1 light of outdoor PCB flash; All-in-one board: LED2 light of outdoor PCB flash OUTDOOR ERROR CODE FAULT DESCRIPTION SPARE PART (LED FLASH TIMES) Indoor PCB Indoor and Communication fault between indoor Outdoor PCB Outdoor and outdoor units...
Page 30
Service Diagnosis OUTDOOR ERROR CODE FAULT DESCRIPTION SPARE PART (LED FLASH TIMES) Lack of refrigerant Refrigerant 4-way valve reverse failure 4-way valve Power over/under voltage protection Power module Outdoor pipe temperature sensor High pressure protection Outdoor PCB Outdoor coil temperature sensor Defrost temperature sensor Power module Outdoor Alternating current over...
Page 31
Service Diagnosis 10.4.1 Thermistor or Related Abnormality Indoor Display E1: Room temperature sensor failure E2: Heat-exchange sensor failure Outdoor display LED1 flash 10 times Defrost temperature sensor failure LED1 flash 11 times Suction temperature sensor failure LED1 flash 12 times Ambient temperature sensor failure LED1 flash 13 times Discharge temperature sensor failure Method of Malfunction...
Page 32
Service Diagnosis 10.4.2 EEPROM abnormal E4: Indoor EEPROM error Indoor Display Indoor display F12: Outdoor EEPROM error; Outdoor LED1 flash 1 times Method of Malfunction The Data detected by the EEPROM are used to determine MCU Detection Malfunction When the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed...
Page 33
Service Diagnosis Indoor DC fan motor malfunction 10.4.3 Indoor Display E14 Indoor DC fan motor malfunction Method of When the fan motor is running, the speed detected by the Hall IC is used to judge the Malfunction abnormal operation of the fan motor Detection Malfunction When the detected rotation feedback signal don’t received in 2 minutes...
Page 34
Service Diagnosis Turn on the unit and check if Measure whether there is a voltage the motor can run pulse (0-15VDC) between 4 and 5 of the CN9 terminal on the indoor PCB The indoor motor is damaged Is it ok? and need replace The indoor PCB is damaged and need replace...
Page 35
Service Diagnosis 10.4.4 Outdoor DC fan motor fault Outdoor display F8 LED1 flash 9 times Method of DC fan motor is detected by checking the fan running condition and so on Detection Malfunction When the detected rotation feedback signal don’t received i n2 minutes Decision Conditions ■...
Page 36
Service Diagnosis The resistances The module PCB is between black line and The resistances are damaged, replace it red line, between black more than 40kΩ with a new one. line and white line of the fan terminal of outdoor PCB are greater than 10MΩ...
Page 37
Service Diagnosis 10.4.5 IPM protection Outdoor display: F1 LED1 flash 2 times Method of IPM protection is detected by checking the compressor running condition and so on Malfunction Detection The system leads to IPM protection due to over current Malfunction Decision The compressor faulty leads to IPM protection Circuit component of IPM is broken and led to IPM protection...
Page 38
Service Diagnosis 10.4.6 Over-current of the compressor Outdoor Display F22, F2, F23 LED1 flash 3 or 24 or 25 times Method of The current of the compressor is too high Malfunction Detection Malfunction When the IPM Module is damaged or the compressor is damaged. Decision Conditions Power supply voltage is too low or too high...
Page 39
Service Diagnosis 10.4.7 The communication fault between IPM and outdoor PCB Outdoor display: F3 LED1 flash 4 times Method of Malfunction Communication is detected by checking the IPM module and the outdoor PCB Detection Malfunction ■ The outdoor PCB broken leads to communication fault Decision ■...
Page 40
Service Diagnosis 10.4.8 Power Supply Over or under voltage fault Outdoor display: F19 LED1 flash 6 times An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit. Method of The power supply is over voltage Malfunction Detection Malfunction...
Page 41
Service Diagnosis 10.4.9 Overheat Protection for Discharge Temperature Outdoor display: F4 LED1 flash 8 times Method of Check the control of the discharge temperature by the temperature detected by the Malfunction discharge pipe thermistor Detection Malfunction When the compressor discharge temperature is above 110℃ Decision Conditions ■...
Page 42
Service Diagnosis 10.4.10 The communication fault between indoor and outdoor Split board Indoor display E7 outdoor display LED1 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB. Malfunction Detection Malfunction The outdoor PCB broken leads to communication fault. Decision The indoor PCB broken leads to communication fault.
Page 43
Service Diagnosis Check the indoor PCB: only indoor charged measure the voltage between 3 and 4 of IC6 on the indoor PCB with a universal meter. And measure the voltage between CN23(S) and CN17 (L) with a universal meter. If the voltage is a constant value from DC 0V to DC 5V.Or The indoor PCB is the voltage between...
Page 44
Service Diagnosis Remove fan motor after Fan motor is switch off the power and damaged. And restart the unit, the LED replace it with a new 1 becomes light or flash. one. Test the fan motor terminal resistance between pin 1(310V) and pin 4(0V), or pin 5(15V) and pin 4(0V) of CN21 are close to 0mΩ...
Page 45
Service Diagnosis All-in-one board Indoor display E7 outdoor display LED2 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB. Malfunction Detection The outdoor PCB broken leads to communication fault. Malfunction The indoor PCB broken leads to communication fault. Decision ...
Page 46
Service Diagnosis Check the indoor PCB: Only indoor charged measure the voltage between 3 and 4 of IC6 on the indoor mainboard with a universal meter. And measure the voltage between CN23(S) and CN52 (L) with a universal meter. If the voltage is a constant value of 0V DC to 5V DC .Or the voltage between communication line (red) The indoor PCB is damaged;...
Page 47
Service Diagnosis Remove fan motor after switch off the power and Fan motor is damaged. Replace restart the unit, the LED 2 it with a new one. becomes light or flash. Test the fan motor terminal resistance between pin 1 (310V) and pin 4 (0V), or pin5 (15V) and pin4 (0V) of CN21 are close to 0mΩ...
Page 48
Service Diagnosis 10.4.11 Loss of synchronism detection (Compressor position detection circuit fault) Outdoor Display F11 LED1 flash 18 times F28 LED1 flash 19 times Method of The position of the compressor rotor can’t detected normally Malfunction Detection Malfunction When the wiring of compressor is wrong or the connection is poor; Decision Or the compressor is damaged Conditions...
Page 49
Service Diagnosis 10.4.12 High work-intense protection Outdoor display E 9 LED1 flash 21 times High work-intense control is activated in the heating mode if the temperature Method of being sensed by the heat exchanger thermistor exceeds the limit. Malfunction Detection Malfunction Activated when the temperature being sensed by the heat exchanger rises above 65℃...
Removal Procedure 12. Removal Procedure Removal of front panel Indoor unit 1. Remove the front panel Step Procedure Points 1.Features 2.Remove the front panel Release the tape Hold the front panel by the tabs on the both sides and lift it until it stops with a click.
Page 53
Removal Procedure Step Procedure Points Loosen the screw and lift up the control box cover Pull the wires out of the control box and then release the pivots on both sides of the unit to remove the front panel. Domestic Air Conditioner...
Page 54
Removal Procedure 2. Remove the air filters and horizontal flap Remove the air filters Step Procedure Points Lift the right air filter upwards slightly and then pull it out downwards Lift the left air filter Upwards slightly and then pull it out downwards Remove the horizontal flap...
Page 55
Removal Procedure 3. Removal of Fan motor and fun Removal of Lower trim panel Step Procedure Points Release ■release two catches fast-assembling lock catch and then remove the (2EA)and loosen the screw panel . under the right lock catch ③ ①...
Page 56
Removal Procedure Removal of base frame A Step Procedure Points Release the the marked fast-assembling lock catch (2EA) ① ② Remove the drainage pipe ① and pull the wires out of the joint box (If the uppermost terminal blocked, remove the Eco Sensor before removing this terminal ) Grip the marked position...
Page 57
Removal Procedure Removal of Fan motor and Step Procedure Points Loosen the marked screws(2EA) and release the cover of fan motor Loosen the marked screw (1EA) and then lift up the fan motor and remove it. Lift up the fan and remove it Domestic Air Conditioner...
Page 58
Removal Procedure 4.Remove the casing Step Procedure Points Loosen the marked screw (2EA) HOLE (4EA) ■When assembling, Release the marked install the front hooks (4EA) and then grille horizontally Pull the grille out so as not to stuff Horizontally and the flap inside.
Page 59
Removal Procedure 5. Release stepping motor wires and the control box Step Procedure Points Remove stepping motor wires and fun motor wires from the Appliance Control Board, then Pull the of the wires out of the control Loosen the control Box screws (1EA) and then pull it.
Page 60
6. Removal of Heat Exchanger Release stepping motor Step Procedure Points ①Loosen the marked screws(1EA) ②Pull mounting plate and heat exchanger ③ bracket, and then remove them. ③ Release the fixture ① plate from the base Frame hook and remove it. ②...
Page 61
86-300 Grudziądz +48 723 737 378 www.haier-ac.pl Producent: Qingdao Haier Air Conditioner Electric Co., Ltd. Haier lndustrial Park, Qianwangang Road, Eco-Tech Development Zone, Qingdao 266555, Shandong, R.P.C. +86 532 88936943 www.haier.com Haier zastrzega sobie prawo do wprowadzania zmian bez wcześniejszego powiadomienia.