Mitsubishi Electric CITY MULTI PFFY-WL20VEM-A Installation Manual
Mitsubishi Electric CITY MULTI PFFY-WL20VEM-A Installation Manual

Mitsubishi Electric CITY MULTI PFFY-WL20VEM-A Installation Manual

Indoor unit

Advertisement

Quick Links

<ORIGINAL>
Air-Conditioners
INDOOR UNIT
PFFY-WL20,25,32,40,50VEM-A
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d'aria.
ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για ασφάλεια και σωστή χρήση, παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο εγκατάστασης πριν αρχίσετε την εγκατάσταση της μονάδας κλιματισμού.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
INSTALLATIONSMANUAL
Læs venligst denne installationsmanual grundigt, før De installerer airconditionanlægget, af hensyn til sikker og korrekt anvendelse.
INSTALLATIONSHANDBOK
Läs den här installationshandboken noga innan luftkonditioneringsenheten installeras, för säker och korrekt användning.
MONTAJ ELKİTABI
Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz.
РЪКОВОДСТВО ЗА МОНТАЖ
За безопасна и правилна употреба, моля, прочетете внимателно това ръководство преди монтажа на климатизатора.
PODRĘCZNIK INSTALACJI
W celu bezpiecznego i poprawnego korzystania należy przed zainstalowaniem klimatyzatora dokładnie zapoznać się z niniejszym podręcznikiem instalacji.
INSTALLASJONSHÅNDBOK
For sikker og riktig bruk, skal du lese denne installasjonshåndboken nøye før du installerer klimaanlegget.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до выполнения установки кондиционера.
PŘÍRUČKA K INSTALACI
V zájmu bezpečného a správného používání si před instalací klimatizační jednotky důkladně pročtěte tuto příručku k instalaci.
NÁVOD NA INŠTALÁCIU
Pre bezpečné a správne použitie si pred inštalovaním klimatizačnej jednotky, prosím, starostlivo prečítajte tento návod na inštaláciu.
TELEPÍTÉSI KÉZIKÖNYV
A biztonságos és helyes használathoz, kérjük, olvassa el alaposan ezt a telepítési kézikönyvet, mielőtt telepítené a légkondicionáló egységet.
PRIROČNIK ZA NAMESTITEV
Za varno in pravilno uporabo pred namestitvijo klimatske naprave skrbno preberite priročnik za namestitev.
MANUAL CU INSTRUCŢIUNI DE INSTALARE
Pentru o utilizare corectă şi sigură, vă rugăm să citiţi cu atenţie acest manual înainte de a instala unitatea de aer condiţionat.
PRIRUČNIK ZA UGRADNJU
Radi sigurne i ispravne uporabe, temeljito pročitajte ovaj priručnik prije ugradnje klimatizacijskog uređaja.

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric CITY MULTI PFFY-WL20VEM-A

  • Page 1 <ORIGINAL> Air-Conditioners INDOOR UNIT PFFY-WL20,25,32,40,50VEM-A INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen. MANUEL D’INSTALLATION Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte. INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
  • Page 2 [Fig. 1.4.1] A Air vent valve [Fig. 3.1.1] (Unit: mm) For PFFY-WL-VEM-A (mm) Model name · · 1142 · 1342 A Floor B Wall C Ceiling D Secure large enough space to prevent that blowout air is blocked. (≥ 100) (≥...
  • Page 3 [Fig. 4.1.1] For fixing on the floor <Viewed from top of the unit> (Unit: mm) For PFFY-WL-VEM-A (mm) Model name · · · Wall [Fig. 4.1.2] For fixing on the wall <Viewed from front of the unit> (Unit: mm) For PFFY-WL-VEM-A (mm) Model name ·...
  • Page 4 [Fig. 4.3.1] [Fig. 4.3.2] Cover Front panel [Fig. 4.3.3] Front panel [Fig. 4.3.4] [Fig. 4.3.5] Side panel [Fig. 4.3.6] Leave an equal amount of clearance on the right and left.
  • Page 5 [Fig. 4.4.1] [Fig. 4.4.3] Cover [Fig. 4.4.2] Cover for leg [Fig. 4.5.1] [Fig. 4.5.2] Nuts (field supply) Washers M10 hanging bolt (field supply) Floor hole for fixing [Fig. 4.6.1] Cover...
  • Page 6 [Fig. 5.2.1] (Unit: mm) Drain outlet [Fig. 5.3.1] Downward slope 1/100 or more Drain hose (Accessory) Indoor unit Collective piping [Fig. 5.3.2] (Unit: mm) Indoor unit Tie band (accessory) Band fixing part Insertion margin Drain hose (accessory) Drain pipe (O.D. ø32 PVC TUBE, field supply) Insulating material (field supply)
  • Page 7 [Fig. 6.3.1] [Fig. 6.3.2] Locally procured insulating material for (Unit: mm) pipes Bind here using band or tape. Do not leave any opening. Lap margin: more than 40 mm Insulating material (field supply) Unit side insulating material There may be a gap between the pipe cover on the unit side and the joint, depending on the joint selected.
  • Page 8 [Fig. 7.1.1] Ground-fault interrupter Local switch/Wiring breaker ~220-240V Indoor unit Pull box [Fig. 7.2.1] [Fig. 7.2.2] M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 TB15 TB5 TB15 Terminal block for indoor transmission cable Terminal block for outdoor transmission cable Remote controller [Fig. 7.2.3] [Fig.
  • Page 9 [Fig. 7.4.1] [Fig. 7.4.2] Screw holding cover (4pcs.) Cover Terminal bed box Knockout hole Remove [Fig. 7.4.3] Use a cable tie to secure the cable. Use PG bushing to keep the weight of the cable and external force from being applied to the power supply terminal connector.
  • Page 10 [Fig. 7.7.1] SW21 SW14 SW12 SW11 <Indoor controller board>...
  • Page 11: Table Of Contents

    • Use the specified cables for wiring. Make the connections securely so that operated forcibly, or parts other than those specified by Mitsubishi Electric are the outside force of the cable is not applied to the terminals. used, fire or explosion may result.
  • Page 12: Before Getting Installed

    1.2. Before getting installed • Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent con- Caution: densation. • Do not install the unit where combustible gas may leak. - Improper drain piping may cause water leakage and damage to furniture and - If the gas leaks and accumulates around the unit, an explosion may result.
  • Page 13: Installing The Unit

    4. Installing the unit 4.1. Selecting the installation method 4.4. Installing the legs for floor-standing installation Install the indoor unit on a load bearing floor or wall. The legs are not used when installing the unit on a wall. The unit can be fixed in place in the following ways to prevent it from falling over. 1.
  • Page 14: Connecting Drain Pipe

    5. Connecting drain pipe To avoid dew drops, provide sufficient antisweating and insulating work to the • Put the end of the drain piping in a position where no odor is generated. drain pipes. • Do not put the end of the drain piping in any drain where ionic gases are gener- 5.1.
  • Page 15: Water Pipe Insulation For Connection With Hbc Unit

    • Leave the pipe-holding sheet metal as it is ([Fig. 6.3.2] (P.7) C). If the pipe is 10. HBC water pipe connection sizes Connection size Pipe size Water connected without the sheet metal in place, undue force may be applied to the Unit model volume (ℓ) Water inlet...
  • Page 16: Water Treatment And Quality Control

    6.5. Water treatment and quality control • Insulation materials for the pipes to be added on site must meet the following specifications: To preserve water quality, use the closed type of water circuit. When the circulating water quality is poor, the water heat exchanger can develop scales, leading Branch piping for indoor unit or 20 mm or more to a reduction in heat-exchange power and possible corrosion.
  • Page 17: Electrical Wiring

    7. Electrical wiring Precautions on electrical wiring 5. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken. Warning: 6. Be sure to connect control cables to the indoor unit, remote controller, and the Electrical work should be done by qualified electrical engineers in accordance outdoor unit.
  • Page 18: Connecting Remote Controller, Indoor And Outdoor Transmission Cables

    *1 The Ground-fault interrupter should support Inverter circuit. The Ground-fault interrupter should combine using of local switch or wiring breaker. *2 Please take the larger of F1 or F2 as the value for F0. F1 = Total operating maximum current of the indoor units  1.2 F2 = {V1 ...
  • Page 19: Connecting Electrical Connections

    7.4. Connecting electrical connections 4. Install a band on the optional lead wire, and perform measures against tension. Please identify the model name of the operation manual attached on the terminal [Fig. 7.5.3] (P.9) box cover with that shown on the rating name plate. C Optional VALVE KIT lead wire 1.
  • Page 23 ±10 IP20 R-718(WATER)
  • Page 24 This product is designed and intended for use in the residential, commercial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN VG79F069H01_en...