Caution!
Risk of overload of the power cable.
To protect the power cable against overload maximum 10 cabinets shall be wired
in a row at 100 V AC or 20 modules at 240 V AC. The total load must not exceed
16 A per cable.
The limit values specified in the technical data must never be exceeded.
Only operate the system with supplied accessories (cables, power distribution, assist grip,
transport carts). However, a power cord to supply power is not included (see 3.1 Scope of
Delivery).
Do not operate or touch the system with wet hands.
Use the provided transition ramps (cable channels). Protect the cable against kinks and sharp
edges.
Notice
Use a TN-S power distribution system with a separate neutral and grounding conductor. Due to
voltage differences in the neutral conductor, large ground current loops can be avoided
therewith.
The complete electrical system should be protected by an appropriately rated disconnect switch,
circuit breakers, over voltage protector and Ground Fault Current Interrupters.
The power system needs to be installed according to the local electrical installation codes. For
Europe, installations have to be conform to DIN-EN 60364 – the standard for electrical
installation of buildings, (and related harmonized Norms). In Germany, the VDE 0100 should be
followed and adhered to.