Outdoor unit
L1
H1
Maximum length of total pipe
L1 + L2 + L3 = 100m
Maximum length of branch piping
L2 = 20m
L3 = 20m
Maximum height between indoor and outdoor units
H1 = 30m
Maximum height between indoor units
H2 = 0.5m
2017.09.05
LIMITATION OF PIPE CONNECTION
Twin type
Branch pipe
UTP-SX272A
L3
L2
Indoor unit (2)
Indoor unit (1)
Outdoor unit
H1
Indoor unit (3)
H2
Triple type
L1
Branch pipe
UTP-SX372A
L4
L2
Indoor unit (1)
Maximum length of total pipe
L1 + L2 + L3 + L4 = 100m
Maximum length of branch piping
L2 = 20m
L3 = 20m
L4 = 20m
Maximum height between indoor and outdoor units
H1 = 30m
Maximum height between indoor units
H2 = 0.5m
L3
Indoor unit (2)
H2
14