5-4. Indoor unit fan motor

¢ Models: AUXG07–18KVLA
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
→ If fan or bearing is abnormal, replace it.
Check point 2. Check resistance of indoor fan motor
Refer to below. Circuit-test "Vm" and "GND" terminal
NOTE: Vm: DC voltage, GND: Earth terminal
→ If they are short-circuited (below 300 kΩ), replace indoor fan motor and controller PCB.
Pin number
(wire color)
1 (Red)
2
3 (Black)
4 (White)
5
6
7 (Yellow)
8 (Brown)
5-4. Indoor unit fan motor
Terminal function
(symbol)
DC voltage (Vm)
No function
Ground terminal (GND)
Control voltage (Vcc)
No function
No function
Speed command (Vsp)
Feed back (FG)