6.3 Introduction of Basic Mode Function

1. Temperature Parameter
◆ Indoor setting temperature (T
◆ Indoor ambient temperature (T
2. Basic Functions of System
After the unit is energized, the interval of start-up time for compressor is no less than 3min under any conditions; when the
compressor is started, the unit is off without the temperature change in 6min.
2.1 Cool Mode
2.1.1 Working conditions and process of cooling
≥T
+ 1
a) When T
abm.
preset
runs under preset fan speed.
≤ T
b) When T
- 1
abm.
preset
o
c) When T
- 1
C (2
preset
Under this mode, the temperature setting range is 61
a) Under cooling mode, after 1h of setting sleep process, Tpreset increases 2
the setting temperature never increases, but the upper limit of increased setting temperature is 86
b) Under heating mode, after 1h of setting sleep process, Tpreset decreases 2
the setting temperature never decreases, but the upper limit of decreased setting temperature is 61
c) There is no sleep function under fan and dry mode.
d) When set sleep function, shift mode will cancel sleep function.
e) The setting temperature display is the same with remote controller; it is not influenced by the setting temperature increases/
decreases.
2.2 Auto Fan
a) Auto fan speed under
Tamb≥Tpreset+4
o
o
F(2
Tpreset<Tamb.< Tpreset+4
Tamb≤Tpreset Low fan
b) There is 3.5min delay for auto fan shift.
2.3 TIMER Function
● General timer
a) TIMER ON: It can set timer on when the system is off, the setting time range is 0.5h-24h, when the time of setting timer on
reaches, and the system runs with the previous setting mode.
b) TIMER OFF: It can set timer on when the system is on, the setting time range is 0.5h-24h, when the time of setting timer off
reaches, the system stop to work.
● Clock timer
a) TIMER ON: If set timer on when the system is running, it continues to run; if set timer on when the system is off, when the time of
setting timer on reaches, and the system runs with the previous setting mode.
b) TIMER OFF: If set timer off when the system is off, the system keeps the stand-by status when setting timer off; if set timer off
when the system is on, when the time of timer off reaches, the system stops to run.
2.4 Memory Function
The system memories the setting running status of previous power-off, and runs automatically with the setting running status before it
power-off when it is energized again. If the unit is on before power-off, the compressor will 3min delay protection when it is energized
again.
2.5 Indicator Lamp, dual-8 digital pipe
a) When the unit runs, under cooling mode, cooling indicator lamp lights, dual-8 displays preset temperature.
b) When the unit runs, under fan mode, fan indicator lamp lights, dual-8 does not display.
c) When the unit runs, under dry mode, dry indicator lamp lights, dual-8 does not display.
d) When the unit runs, under heating mode, heating indicator lamp lights, dual-8 displays preset temperature.
)
preset
)
amb.
o
o
C (2
F), the unit will start to run in cooling mode, the compressor and kick motor start to run, and fan motor
o
o
C (2
F), the compressor and kick motor stop to run, and fan motor runs under preset fan speed.
+ 1
o
o
o
F)<T
<T
C (2
F), the unit will keep the current running status.
amb.
preset
Tamb.
Tpreset +1 ˚C
Tpreset –1 ˚C
Compressor
Outdoor fan
Indoor fan
Cooling mode;
C)
High fan;
o
o
F(2
C)
Med fan;
o
o
o
o
F-86
F (16
C -30
C ).
≥ 6 min.
≥ 3 min.
≥ 6 min.
Setting fan speed
Run
Stop
o
Start cooling
Original operating status
Stop cooling
o
o
F(1
C); 2h later, Tpreset increases 4
o
o
F(30
C)
o
F(1
C); 2h later, Tpreset decreases 4
o
o
F(16
C)
o
o
F(2
C). After 2h,
o
o
F(2
C). After 2h,
22