Fujitsu AirStage ASHA18GATH Installation Manual page 10

Hide thumbs Also See for AirStage ASHA18GATH:
Table of Contents

Advertisement

Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
Load
resistance
Load
resistance
connected unit
● Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
*c
*c
Ch 1
Ch 2
*c
Ch 3
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suffi ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
En-9
DC power supply
*1
12 to 24V
DC power supply
12 to 24V
P.C.B
GND
*d
P.C.B
CNA01
*b
Input device 1
CNA03
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
Operation behavior
● Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
DIP switch [Set 2 SW2]
OFF (Factory setting)
● When function setting is "Operation/Stop" mode.
[In the case of "Edge" input]
Connector
P.C.B
Ch1 of CNA01 or CNA02
CNA01
P.C.B
[In the case of "Pulse" input]
CNA01
CNA01 or CNA02
P.C.B
* The last command has priority.
CNA01
* The indoor units within the same remote controller group operates in the same mode.
● When function setting is "Emergency stop" mode.
[In the case of "Edge" input]
Connector
Ch1 of CNA01 or CNA02
CNA02
[In the case of "Pulse" input]
CNA04
CNA01 or CNA02
* All indoor units of same refrigerant system stops when Emergency stop operates.
K1
K4
K2
K5
K3
K6
Input device 2
K1 - K6: Relay
(Device for DC Current)
Input signal type
Edge
ON
Pulse
Input signal
OFF → ON
ON → OFF
Connector
Ch1
Ch2
Input signal
OFF → ON
ON → OFF
Connector
Ch1
Ch2
P.C.B
CNA02
P.C.B
CNA02
P.C.B
CNA02
Edge
Pulse
The width of pulse
must be longer than
200msec.
Command
Operation
Stop
Input signal
Command
OFF → ON
Operation
OFF → ON
Stop
Command
Emergency stop
Normal
Input signal
Command
OFF → ON
Emergency stop
OFF → ON
Normal

Advertisement

Table of Contents
loading

Table of Contents