7.1.1 Indoor unit address
• Rotary switch (IU AD × 1)....Factory setting "0"
• Rotary switch (IU AD × 10)....Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A
7.1.2 Refrigerant circuit address
• Rotary switch (REF AD × 1)....Factory setting "0"
• Rotary switch (REF AD × 10)....Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Setting
Setting range
Indoor unit
0 to 63
address
Refrigerant
0 to 99
circuit address
• If working in an environment where the wireless remote controller can be used, the
addresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to "00".
(For information on setting using the wireless remote controller.)
Table A
Address
Rotary Switch Setting
REF AD SW
Refrigerant circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
99
9
Do no t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure .

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
DIP switch
"SET3"
En-11
Type of switch
Setting exam-
ple 2
IU AD × 10
IU AD × 1
Setting exam-
ple 63
REF AD × 10 REF AD × 1
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
9
63
6
Code change
A
B
C
A
B
C
OFF
SW 1
SW 2
DIP switch
"SET3"
SW 3
SW 4
Custom code
DIP switch
A (Factory
SET3
B
setting)
SW1
OFF
ON
SW2
OFF
OFF

7.3. Function setting

Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Filter
indicator
interval
Filter
indicator
action
(Forbidden)
Vertical
airflow
× 1
direction
0
Horizontal
1
swing
2
airflow
3
direction
4
(Forbidden)
5
6
Cool air
7
tempera-
8
ture trigger
9
0
1
Heat air
2
tempera-
ture trigger
3
Auto restart
D
Cool Air
Prevention
D
ON
External
control
Error report
target
C
D
OFF
ON
ON
ON
Fan setting
when
cooling
thermostat
OFF
WARNING
Setting number Default
Adjust the filter cleaning interval noti-
00 Standard
fication. If the notification is too early,
01 Longer
11
change to setting 01. If the notifica-
02 Shorter
tion is too late, change to setting 02.
Enable or disable the filter indicator.
00 Enable
Setting 02 is for use with a central
01 Disable
remote controller.
Display
13
only on
02
central
remote
controller
20
00
Adjust the vertical airflow direction.
00 Standard
23
01 Adjust
Adjust the horizontal swing airflow
00 Standard
direction.
01 Left half
24
(For horizontal swing equipped
02 Right half
models)
27
00
Adjust the cool air trigger tempera-
00 Standard
ture. To lower the trigger temperature,
01 Adjust (1)
30
use setting 01. To raise the trigger
02 Adjust (2)
temperature, use setting 02.
Adjust the heat air trigger
00 Standard
temperature. To lower the trigger tem-
01 Adjust (1)
perature by 6 degrees C, use setting
02 Adjust (2)
31
01. To lower the trigger temperature
by 4 degrees C, use setting 02. To
03 Adjust (3)
raise the trigger temperature, use
setting 03.
00 Enable
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
40
01 Disable
Restrain the cold airflow with making
00 Super low
the airflow lower when starting heat-
Follow the
ing operation. To correspond to the
43
setting on
ventilation, set to 01.
01
the remote
controller
Allow an external controller to start
00 Start/Stop
or stop the system, or to perform an
Emergency
01
emergency stop.
stop
* If an emergency stop is performed
46
Forced
* If forced stop is set, indoor unit
02
Stop
Change the target for reporting
00 All
errors. Errors can either be reported
Display
in all locations, or only on the central
only on
47
remote controller.
01
central
remote
controller
Follow the
When set to 01, the fan stops when
setting on
the thermostat is OFF in cooling
00
the remote
operation. Connection of the wired re-
49
controller
mote controller (2-wire type or 3-wire
type) and switching its thermistor are
01 Stop
necessary.
Details
tion such as for power failure etc.
Do not start and stop the indoor unit
by this function in normal operation.
Be sure to operate by the control
unit, converter or external input
device.
from an external controller, all re-
frigerant systems will be disabled.
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.