Mitsubishi Electric SEZ-KD12NA4R1.TH Installation Manual page 4

Table of Contents

Advertisement

Available languages

Available languages

[Fig. 6-10]
Max. 20m [65 ft]
1.5-2 m [5 to 7 ft]
B
A
K
B
D
E
F
F
[Fig.6-11]
K
J
A
B
35
[1-13/32]
25 [1]
C
D E
A Indoor unit
B Pipe cover (60 mm [3/8 in]) (accessory)
C Tie band (accessory)
D Visible part
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supplied)
H Insulating material (field supplied)
I Tie band (accessory)
J Max.180 ± 5 mm [7-3/32 ± 7/32 in]
K No gap. The joint section of the insulation material must meet at the top.
[Fig. 6-13]
A
B
E
F
A Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in].
B Remove the water supply port.
C About 2 liters
D Water
E Filling port
F Screw
4
C
L
M
D
D
F
G
I
H
(Unit: mm [in])
G
F
H
25 [1]
E
I
C
D
6.5
Max. 300 mm [11-13/16 in]
N
B
J
F
O
[Fig.6-12]
B
A
5
D
A Indoor unit
B Pipe cover (30 mm [3/16 in]) (accessory)
C Tie band (accessory)
D Band fixing part
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 PVC TUBE, field supplied)
H Insulating material (field supplied)
I Max.145 ± 5 mm
6.6
[Fig. 6-14]
<Indoor board>
Correct piping
Wrong piping
A Insulation (9 mm [3/8 in] or more)
B Downward slope (1/100 or more)
C Support metal
K Air bleeder
L Raised
M Odor trap
Grouped piping
D O. D. ø32 mm [1-1/4 in] PVC TUBE
E Make it as large as possible. About 10 cm [3-15/16 in].
F Indoor unit
G Make the piping size large for grouped piping.
H Downward slope (1/100 or more)
I O. D. ø38 mm [1-1/2 in] PVC TUBE for grouped piping.
(9 mm [3/8 in] or more insulation)
J Up to 550 mm [21-21/32 in]
N Drain hose (accessory)
O Horizontal or slightly upward
I
G
F
H
25