4.3.2.
Assigning IP addresses (c504, c505 - c516)
The address is assigned according to setting of c504 (IP mode).
c504
0
The option uses the address defined in c505-c516.
1
Don't use on this product.
2
The option receives its address from DHCP server.
*Setting device name (c081-c096) is required.
3
The option receives its address from DCP server..
When you setup the IP address by manual (c504 = 0), inverter needs 4 settings.
IP address of the inverter
Subnet mask
Gateway address
These parameters are effective settings at c504 = 0 (IP mode: Manual).
If you set a value other than 0 to c504, these parameters are invalid.
After dynamic addressing by DHCP server or DCP server, the new address values are displayed in the
parameters c524 - c535.
Case of automatic switching of c504 (IP mode) to 3 (DCP)
Needed conditions:
- The device has a Station Name (*1) configuration and validation
- The device is connected to a PROFINET controller (PLC)
- The PROFINET controller (PLC) has the Station Name (*1) in its own configuration
- The settings are in local configuration of the PROFINET controller (PLC)
If all of these conditions are fulfilled:
- c504 (IP mode) is automatically set to 3 (DCP), and c505 - c516 are set to 0.
- IP settings are replaced by the one set in local PROFINET controller (PLC)
- The new configuration is applied immediately
(*1): Depending on the configuration tool you may be referred to as a "device name".
This is different from the device name that is set in the inverter parameters c081-c096. Station
name will be set / assigned by the configuration tool for PROFINET.
Comments
(c505 - c508)
(c509 - c512)
(c513 - c516)
- 26 -